Chapter 5
– Parameter List
5-8
CODE
Comm.
Addr
Description
LCD Keypad
Display
Setting Range
Factory
Default
Adj.
During
Run
Page
FU2-40 9328
Motor Capacity
selection
Inverter (5.5 ~ 450 kW)
Motor select
0 (0.75kW)
1 (1.5kW)
2 (2.2kW)
3 (3.7kW)
4 (5.5kW/)
5 (7.5kW/)
6 (11.0kW)
7 (15.0kW)
8 (18.5kW)
9 (22.0kW)
10 (30.0kW)
11 (37.0kW)
12 (45.0kW)
13 (55.0kW)
14 (75.0kW)
15 (90.0kW)
16 (110.0kW)
17 (132.0 kW)
18 (160.0 kW)
18 (220.0 kW)
20 (280.0 kW)
21 (315.0 kW)
22 (375.0 kW)
23 (450.0 kW)
Depending
on the
inverter
capacity
X
6-25
* A motor rating same as inverter capacity is automatically set. If different, set the correct value.
FU2-41 9329 Number of Motor Poles Pole number
2 to 12
4
X
6-25
FU2-42 932A
Motor Slip
Rate-Slip
0.00 to 10.00
Depending
on the
motor
capacity
X
6-25
FU2-43 932B
Rated Current of Motor
(rms)
Rated-Curr
1.0 to 999.9[A]
X
FU2-44 932C
No Load Motor Current
(rms)
Noload-Curr
0.1 to 999.9
X
FU2-46 932E
Load Inertia
Inertia rate
0 to 40
10
X
FU2-47 932F
Gain for Motor Speed
Display
RPM
DisplayGn
1 to 1000 [%]
100 [%]
O
FU2-48 9330
Carrier Frequency
Carrier freq
5.5~22kW 0.7~15 [kHz]
5.0 [kHz]
O
6-26
30kW
0.7~10 [kHz]
37~75kW 0.7~4 [kHz] 4.0 [kHz]
90~280kW 0.7~3 [kHz] 3.0 [kHz]
315~450kW 0.7~2[kHz]
2.0 [kHz]
FU2-49 9331
PWM Type Selection
PWM
Technique
0
(Normal)
0 (Normal )
X
6-26
1
(Low leakage)
FU2-52 9334 Safety Stop Dec. Rate Dec Rate
1.0 - 100.0 [sec]
100.0 [sec]
-
6-26
FU2-53 9335
Safety Stop Output
Dec. Rate
safety_perc
2 - 500
21
-
6-26
FU2-60 933C Control Mode Selection Control Mode
0
(V/F)
0 (V/F)
X
6-27
1
(Slip compen)
2
(Sensorless)
FU2-61 933D Auto Tuning Selection AutoTuneEnbl
0
(No)
0 (No)
X
6-28
1
(Static)