Chapter 4 - Operation
4-18
4.4 Operation Example
Operation
Example (1)
V/F C Analog Voltage Input (V1) + Operation via Terminal (FX/RX)
[Operation condition]
-. Control mode : V/F control
-. Frequency command : 50[Hz] analog input via V1 terminal
-. Accel/Decel time : Accel
– 15 [sec], Decel – 25 [sec]
-. Drive mode : Run/Stop via FX/RX terminal, Control terminal : NPN mode
[Wiring]
R(L1)
S(L2)
T(L3)
G
U
V
W
M8(RX)
M7(FX)
M6
M5
M4
M3
M2
M1
CM
V+
V1
5G
S1
5G
3A
3C
3B
IM
3P
AC
INPUT
Potentiometer
2[kohm],1/2W
S/
W
S0
Step Parameter setting
Code
Description
1
Control Mode
Selection
FU2-60 Set it to 0 {V/F}.
2
Drive Mode
DRV-3 Set it to Fx/Rx-1.
3
Frequency Mode
DRV-4 Set V1 Analog input value in frequency mode.
4
50[Hz] freq
command setting
DRV-0 Set freq command 50[Hz] via V1 (potentiometer).
5
Accel/Decel time
DRV-1
DRV-2
Set Accel time to 15 [sec] in DRV-2.
Set Decel time to 25 [sec] in DRV-3.
6
Terminal FX
I/O-26
Motor starts to rotate in Forward direction at 50Hz with
Accel time 15 [sec] when FX terminal is turned ON.
Motor decelerates to stop with Decel time 25[sec] when
FX terminal is turned OFF.
7
Terminal RX
I/O-27
When RX terminal is turned ON motor starts to
rotate in Reverse direction at 50[Hz] with Accel
time 15 [sec]. When it is OFF, motor decelerates
to stop with Decel time 25 [sec].
☞
0.75 ~ 30 kW products: Common terminal of frequency setting is 5G terminal.
☞
37 ~ 450 kW products: Common terminal of frequency setting is CM terminal.