Chapter 4 - Operation
4-20
Operation
Example (3)
V/F c Analog input (V1S) + Operation via terminal FX/RX
[Operation condition]
-. Control mode : V/F control
-. Frequency command : Setting 50[Hz] via Analog input (V1S)
-. Accel/Decel time : Accel time 15 [sec], Decel time 25 [sec]
-. Drive mode : Run/Stop via FX/RX, Control terminal: NPN mode
[Wiring]
R(L1)
S(L2)
T(L3)
G
U
V
W
M8(RX)
M7(FX)
M6
M5
M4
M3
M2
M1
CM
V+
V1
V-
S1
5G
3A
3C
3B
IM
3P
AC
Input
Potentiometer
2[kohm],1/2W
S/W
S0
Step
Parameter setting
Code
Description
1
Control mode
selection
FU2-60 Set it to 0 {V/F}.
2
Drive mode
DRV-3 Set it to 1 {Fx/Rx-1}.
3
Frequency mode
DRV-4 Set it to 3 {V1S}.
4
Operating frequency
command 50[Hz] setting
DRV-0 Set 50[Hz] via potentiometer (V1S).
5
Accel/Decel time
setting
DRV-1
DRV-2
Set Accel. time to 15[sec] in DRV-1 with Decal.
time to 25[sec] in DRV-2.
6
FX terminal (M7)
IO-26
When FX terminal is turned ON, motor rotating in
forward direction starts running at 50[Hz] for 15 [sec].
When FX terminal is turned OFF, motor decelerates
to stop for 25[sec].
7
RX terminal (M8)
IO-27
When RX terminal is turned ON, motor rotating in
reverse direction starts running at 50[Hz] for 15[sec].
When RX terminal is turned OFF, motor decelerates
to stop for 25 [sec].
☞
Note: V1S mode enables Forward/Reverse rotation using ±12V power via Analog
input command.
☞
Note: Use V1 instead of V1S mode when FWD/REV Run Prevention is active. V1S
mode enables the motor to run both FWD/REV directions.