Chapter 4 - Operation
4-13
4) Sensorless vector control
Set FU2-
60 to “Sensorless” to enable Sensorless vector control. It is strongly
recommended to perform
Auto-tuning
before starting Sensorless control in order
to maximize performance.
Parameter Name
Code
Description
Control method selection
FU2-60
Select Sensorless.
P, I gain for sensorless control
FU2-65, FU2-66
Set gain for Sensorless.
Starting freq
FU1-32
Starting freq of the motor
Note) No-load current for Sensorless control is not entered by auto-tuning. Therefore
enter the no-load current value in V/F operation. When other than LS standard
motor is used, set this value according to the motor in use for better performance.
5) Auto-tuning of motor constant
This parameter enables auto-tuning of the motor constants. If FU2-61 is set to
Yes and press the enter key,
Rs, Lsigma
values begin tuning with the motor
stopped. Refer to motor nameplate for the rest of other parameters.
Parameter Name
Code
Description
Auto-tuning
FU2-61
No, Yes
Note) Motor no-load current and slip freq should be set correctly for safe and better
performance. Be sure to check these values and set them properly.
Refer to Chapter 5, FU2-40~66 for more.
4.3.2
Advanced function setting
SV-iP5A inverter features advanced function parameters to maximize efficiency
and performance of the motor. It is recommended to use the factory setting unless
parameter value change is inevitable.
1) V/F control
Parameter
Name
Code
Description
V/F Pattern
FU1-40
Use it according to load characteristics. If User V/F is selected, user
can select the optimum output V/F characteristic for the application and
load characteristics in [FU1-41]~[FU1-48].
Dwell
operation
FU2-07
FU2-08
Used to output torque in an intended direction. Inverter stops
acceleration for the preset [FU2-08] Dwell time while running at Dwell
frequency [FU2-07] and starts acceleration at commanded frequency.
Setting [FU2-08] Dwell time to 0 disable the Dwell operation.
Jump
Frequency
FU2-10
FU2-1~16
When it is desired to avoid resonance attributable to the natural
frequency of a mechanical system, these parameters allow resonant
frequencies to be jumped. Up to three areas can be set, with the jump
frequencies set to either the top or bottom point of each area. To
enable the function, set [FU2-
10] to ‘Yes’ and set the value in [FU2-
11]~[FU2-16].
Accel/Decel
pattern
S-curve
FU1-2, 3
FU1-4, 5
This pattern has an effect on the prevention of cargo collapse on
conveyor etc. and reduction in an acceleration/ deceleration shock.