USE AND MAINTENANCE MANUAL
– DLC
NET
Series
Use as interface with indicator
LOGIC S.r.l. - M0145Db.docx
Mod. L0006A01 of 30/05/2016
Page 52 of 78
Use the buttons
and
to add the flashing digit and move to
editing to the next. Edit this value of divisions so that the multimeter
indicates 4mA in the case of
setting or 0 mA if
.
Press
to confirm. The display shows the message
, as the
instrument waits for the value of the DAC divisions corresponding to
20mA.
Press
to start editing, edit the value using the buttons
and
until the multimeter does not indicate 20mA (default:
).
Press
to confirm.
The last parameter to edit is if the analogue output must follow the trend of
the net or gross weight. The display shows the message corresponding to
the current set (default
). Use the button
to select
or
. Press
to confirm.
At this point the instrument will show the written
and the
procedure is finished.