USE AND MAINTENANCE MANUAL
– DLC
NET
Series
Installation
LOGIC S.r.l. - M0145Db.docx
Mod. L0006A01 of 30/05/2016
Page 32 of 78
3.8.4
I/O connections in
Batch mode
When the instrument is configured as a dosing device (in
menu is selected
), the instrument uses 8 outputs for the control of solenoid
valves and pumps and an additional input for the Start / Stop button.
Connections are described in Figure 23 and Table 15.
It is necessary the expansion board -EB.
Table 15. I/O connections in Batch mode
Pin on DLC
NET
Description
TB6-1
0 Vdc
TB6-2
Out 1 (+24 Vdc transistor open-collector PNP), solenoid valve output (instant) ingredient 1
TB6-10
Out 2 (+24 Vdc transistor open-collector PNP), solenoid valve output (instant) ingredient 2
TB6-3
Out 3 (+24 Vdc transistor open-collector PNP), solenoid valve output (instant) ingredient 3
TB6-11
Out 4 (+24 Vdc transistor open-collector PNP), solenoid valve output (instant) ingredient 4
TB6-4
Out 5 (+24 Vdc transistor open-collector PNP), pump output (delayed) ingredient 1
TB6-12
Out 6 (+24 Vdc transistor open-collector PNP), pump output (delayed) ingredient 2
TB6-5
Out 7 (+24 Vdc transistor open-collector PNP), pump output (delayed) ingredient 3
TB6-13
Out 8 (+24 Vdc transistor open-collector PNP), pump output (delayed) ingredient 4
TB6-8
+24 Vdc out start/stop push button
TB6-15
In start/stop push button
For the control of solenoid valves and pumps always lean on relay 24Vdc,
max. 50mA (100mA total, a maximum of two simultaneously active outputs).
Figure 23. Input and output connections for dosing
3.8.5
Analog ouput
connection 0-20 mA
or 4-20 mA
The analog output 0-20 mA or 4-20 mA connections are highlighted in the table
and figure below.
It is necessary the expansion board -EB.