background image

6

TNR-I&S-02

VENTING

 CAUTION

The vent shall terminate a minimum of 12 inches above expected
snowfall level to prevent blockage of vent termination.
The horizontal centerline of the exhaust vent terminal (if applicable)
must not be located lower than the horizontal centerline of the air
intake terminal if vented through the same wall.
A service drain loop must be installed in the drain tubing to serve as
a condensate trap to prevent flue gases from escaping in the room.
DO NOT position air intake terminal above exhaust terminal.
NEVER locate air intake terminal when exhaust gases can be introduced.

The venting instructions must be followed to avoid restricted combustion
or recirculation of flue gases.  Such conditions cause sooting or risks of fire
and asphyxiation.

This water heater can be installed as either a direct vent system or power
vent (air from inside) system.  If it is installed as a direct vent system,
then the air intake and the exhaust vent are piped to the outside.  If a
power vented system is used, then air is drawn from inside and only the
exhaust is piped to the outside.  Determine which system is best for your
application and install as described in the following sections.

DIRECT VENT INSTALLATION

Venting may be run horizontally through an outside wall or vertically
through a roof through using either 3 inch (7.6 cm) or 4 inch (10.2 cm)
diameter PVC or CPVC pipe.  This water heater is supplied with a 3 inch PVC
screened intake and exhaust 90° elbow referred to as the exhaust vent
terminal and the air intake terminal.

NOTICE

Before beginning installation of any vent pipe, read the vent pipe
manufacturer’s installation instructions.
Water heater must be protected from freezing downdrafts during
shutdown periods.
Provide protection of the building materials from degradation by flue
gases from the exhaust vent terminal.

 WARNING

The vent system must be properly installed.  Failure to properly install
the vent system could result in property damage, personal injury, or
death.

DO NOT

 install damaged venting system components.  If damage is

evident then please contact the supplier where the water heater was
purchased or the manufacturer listed on the rating plate for
replacement parts.

Use only the vent terminals provided or factory authorized terminals
for venting this water heater.

The water heater requires its own separate venting system.  Do not
connect the exhaust vent into an existing vent pipe or chimney.

All of the exhaust venting connections must be leak checked with a
soap solution upon initial start up of the water heater.  Any leaks must
be repaired before continuing operation of the water heater.

Do not terminate the venting where noise from the exhaust or intake
will be objectionable. This includes locations close to or across from
windows and doors.  Avoid anchoring the vent and intake pipes directly
to framed walls, floors, or ceilings unless rubber isolation pipe hangers
are used.  This prevents any vibrations from being transmitted into the
living spaces.

Do not exceed the venting distances or the number of elbows listed in
this manual. Exceeding the maximum venting distances may cause
the water heater to malfunction or cause an unsafe condition.

DO NOT operate this water heater until the venting installation is
complete and the piping completed. Failure to complete installation
before operation can result in property damage, personal injury, or
death.

Figure 9                                                                  Typical Plumbing Schematic for Zoned Heating

 

TuboCharger  Water Heater

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: