1 1

TNR-I&S-02

COAXIAL VENTING INSTALLATION PROCEDURE

Vertical Installation (Recommended)

1. Become familiar with coaxial vent kit.

2. Determine the best location for the termination kit.

3. Cut the recommended 5" diameter hole.

Through The Wall Venting With Low Ground Clearance:

When venting cannot exit through the wall at a height greater than or
equal to 12" 

(30.5 cm) 

(and above expected snow level) from the ground,

then the installation must be modified as shown below (see Figure 16).
Refer to Tables 2 or 3 for maximum venting lengths using 3” 

(7.6 cm)

 or

4” 

(10.2 cm)

 diameter plastic pipe.

Maximum Vent Length Determination

Determining required vent length:

1. Determine the total length of straight vent pipe (in feet) required.
2. Add 5 feet of venting for every 90° elbow.
3. Add 2 ½ feet of venting for every 45° elbow.
4.

Total vent length can not exceed “Max. Vent
ength” in Table 3.

NOTICE

Do not include the 3" exhaust elbow or vent terminals in determining
maximum vent length.

 WARNING

Improper installation, adjustment, service, or maintenance can cause
property damage, personal injury, or death.  Consult a qualified installer,
service agency, or the gas supplier for information or assistance.
This kit must be used only for terminating this water heater.  Do not
use this termination kit for any other appliance.  Using this kit on other
appliances and/or water heaters can result in property damage, personal
injury, or death.

DO NOT

 operate this water heater until the installation and assembly

of this kit is complete and the piping completed.  Failure to complete
installation before operation can result in property damage, personal
injury, or death.
Before beginning any installation, be sure the main electrical disconnect
switch is in the OFF position.  Electrical shock can cause personal injury
or death.

DO NOT 

operate this water heater with the rain cap removed or

recirculation of combustion products may occur.  Water may also collect
inside larger combustion-air pipe and flow to the burner assembly.
Failure to follow this warning could result in product damage, or improper
operation, personal injury or death.

 CAUTION

DO NOT use field-supplied couplings to extend pipes. Airflow
restriction will occur and the water heater pressure switches may cause
intermittent problems.

 

Figure 18

Concentric Vent Kit Part Identitication

 

Figure 17

Dimensional Layout of Concentric Vent Kit

 

Figure 16

Vent Terminal (Low Ground Clearance)

Table 3

Direct Vent Maximum Vent Length

Storage

Capacity

(Gallons)

Rated

Input

(Btu/Hr)

Max Vent Length (ft)

3" PVC or CPVC

Max Vent Length (ft)

4" PVC or CPVC

6 0
6 0
6 0

1 0 0
1 0 0
1 0 0
1 0 0
1 0 0

125,000
150,000
199,999
150,000
199,999
250,000
300,000
399,999

1 2 0
1 0 0

8 0

1 2 0
1 0 0

8 0
6 0
5 0

1 7 0
1 5 0
1 3 0
1 7 0
1 5 0
1 3 0
1 2 0
1 0 0

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: