1 4

TNR-I&S-02

 CAUTION

The water heater and individual shutoff valve must be disconnected
from the gas  supply piping system during any pressure testing of the
system at test pressures in excess of ½ psi 

(3.5 kPa)

.  The water

heater must be isolated from the gas supply piping system by closing
its manual shutoff valve during any pressure testing of the gas supply
system at test pressures equal to or less than ½ psi

 (3.5 kPa)

.  The

supply line must be capped when not connected to the water heater.
If copper supply lines are used, they must be internally tinned and
certified for gas service.

GAS CONNECTIONS

 WARNING

Turn off or disconnect the electrical power supply to the water heater
before servicing.  Label all wires prior to disconnection when servicing
controls.  Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
All electrical wiring must be installed and grounded in accordance with
local codes, or in the absence of local codes, the National Electrical
Code, ANSI/NFPA 70 and/or CSA C22.2 Electrical Code.

 WARNING

DO NOT USE MATCHES, CANDLES, FLAME OR OTHER SOURCES
OF IGNITION FOR THIS PURPOSE.

 WARNING

Connect this water heater only to the type of gas as shown on the
rating plate.  Use clean black iron pipe or equivalent material approved
by local codes and ordinances.  (Dirt and scale from the pipe can enter
the gas valve and cause it to malfunction).  The inlet gas line must
have at least a 3 inch 

(7.62 cm) 

drip leg (sediment trap) installed as

close to the water heater’s gas valve as possible.  A ground joint union
must be installed in the gas supply line, as close to the water heater as
possible, to permit servicing of the water heater.  Compounds used on
the threaded joints of the gas piping must be resistant to the action of
liquefied petroleum gases/propane gas.  

DO NOT

 apply pipe dope to

the gas valve inlet and make certain that no pipe dope has become
lodged in the inlet screen of the gas valve.  Extreme care must be
taken to ensure no pipe dope enters the gas valve and to avoid
excessive torque when tightening the gas supply line to the gas valve.
Excessive torque may result in cracking of the gas valve housing.  The
suggested maximum torque is 31.5 foot lbs. 

(4.4 kg-m)

. The

manufacturer of this water heater will not be liable for any damage or
injury caused as a result of a cracked gas inlet as a result of excessive
torque.

This water heater and its gas connection must be leak tested before
placing the water heater in operation.  Check for gas leaks with a soap
and water solution and a brush or a commercial leak detector fluid.
NEVER USE A MATCH OR OPEN FLAME FOR TESTING!

The water heater is not intended for operation at higher than 14.0 inch
water column (½ psi) supply gas pressure.  Higher gas supply pressures
require supplemental  reducing service regulation.  Exposure to higher
gas supply pressure may cause damage to the gas controls which
could result in fire or explosion.  If overpressure has occurred such as
through improper testing of gas lines or emergency malfunction of the
supply system, the gas valve must be checked for safe operation.
Make sure that the outside vents on the supply regulators and the
safety vent valves are protected against blockage.  These are parts of
the gas supply system, not the water heater.

The gas supply lines must meet all requirements of the National Fuel Gas
Code ANSI Z223.1 (Latest Edition), or in Canada CAN/CGA B149.1 Natural
Gas Installation Code (Latest Edition) or CAN/CGA B149.2 Propane
Installation Code (Latest Edition).

GAS METER SIZE – NATURAL GAS ONLY

Be sure that the gas meter has sufficient capacity to supply the full rated
gas input of the water heater as well as the requirements of all other gas
fired equipment supplied by the meter.  If the gas meter is too small, ask
the gas company to install a larger meter having adequate capacity.

GAS PRESSURE REGULATION

Main line gas pressure to the water heater should be between a maximum
14.0 inch W.C. and a minimum supply pressure as shown on the rating
plate.  The inlet gas pressure must not exceed the maximum value.

BEFORE PLACING THE WATER HEATER IN OPERATION, CHECK FOR GAS
LEAKAGE.  USE SOAP AND WATER SOLUTION OR OTHER MATERIAL ACCEPTABLE
FOR THE PURPOSE OF LOCATING GAS LEAKS.

ELECTRICAL CONNECTIONS

The water heater must be wired to a 120 VAC, 60 Hz, 15A power supply.
The water heater should be connected to a GFI outlet and wired on a
separate circuit and breaker.  If a flexible line cord and plug is permitted
by local code, then provide a three wire GFI grounding type receptacle
within reach of the line cord provided on the control box.

  DO NOT

 plug

the line cord into a receptacle that can have the power supply interrupted
by a switch that is used to control lights or another appliance.

Figure 22                                         Drip Leg

  

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: