background image

4

TNR-I&S-02

 CAUTION

If sweat fittings are to be used, DO NOT apply heat to the nipples in
front or side of the water heater.  Sweat the tubing to the adapter
before fitting the adapter to the water connections.  It is imperative
that heat is not applied to the nipples containing a plastic liner.

 WARNING

Failure to install and maintain a new, listed temperature and pressure
relief valve will release the manufacturer from any claim, which might
result from excessive temperature and pressures.

Hydrogen gas can be produced in an operating water heater that has
not had water drawn from the tank for a long period of time (generally
two weeks or more).  HYDROGEN GAS IS EXTREMELY FLAMMABLE. To
prevent the possibility of injury under these conditions, we recommend
the hot water faucet to be open for several minutes at the kitchen sink
before you use any electrical appliance, which is connected to the hot
water system.  If hydrogen is present, there will be an unusual sound
such as air escaping through the pipes as hot water begins to flow.  Do
not smoke or have open flame near the faucet at the time it is open.

Keep clear of the combination temperature and pressure relief valve
discharge line outlet.  The discharge may be hot enough to cause scald
injury.  The water is under pressure and may splash.

WATER CONNECTIONS

INSTRUCTIONS FOR CONNECTIONS

1. BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN

WATER SUPPLY VALVE. After shutting off the main water supply,
open a faucet to relieve the water line pressure to prevent any
water from leaking out of the pipes while making the water
connections to the water heater. The COLD water inlet and HOT
water outlet are identified on the water heater.  Make the proper
plumbing connections between the water heater and the plumbing
system to the house. Install a shut-off valve in the cold water
supply line.

2. If this water heater is installed in a closed water supply system, such

as the one having a back-flow preventer in the cold water supply,
provisions must be made to control thermal expansion. DO NOT
operate this water heater in a closed system without provisions for
controlling thermal expansion. Warranties do not cover damages

Figure 6     Typical Four Water Heater Connection

 

 

Figure 3

Typical Front Inlet Connect with Storage Tank

 

Figure 5

Typical Three Water Heater Connection

 

Figure 4

Typical Two Water Heater Connection

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: