2 0

TNR-I&S-02

Make sure that water heater is plugged in.
When the switch is on, is there 120VAC between L1 and N on the terminal block?  If not, then
check for loose wire connections on the “Power Switch Wire Harness.”  If connections are ok, then
replace the switch.
If there is voltage between L1 and N then the light on the switch is burnt out.  Replace switch.

Make sure that the temperature of the tank is cool.
If the thermostat does not call for heat, then check the PRIMARY voltage across the “Transformer”.
If there is voltage across the PRIMARY, then check the voltage across the SECONDARY leads of
the “Transformer”.
Install a jumper wire from N.O. terminal to the COM terminal on the “Thermostat PC Board.”  If
the thermostat calls for heat after installing a jumper wire  then check the “Thermostat Sensor
Probe” leads for proper resistance with an OHM meter (See appendix A).
If sensor reading are not correct, replace “Thermostat Sensor Probe.”
If the sensor readings are correct, then check “Potentiometer” for the proper resistance.  If the
readings are correct, then replace the “Thermostat PC Board”, otherwise replace the
“Potentiometer.”

Check for 120 VAC  at the ignition module on “120 VAC IN.”  If there is voltage, then replace the
ignition module.
If there is not any voltage, check the voltage across the transformer as previously described.

Is the “Vacuum Switch” (air intake switch) N.C.? If no, then check the hose and see if it is filled
with condensate.  If the hose is not filled with condensate, then replace vacuum switch.  If filled,
empty hose.
Is the “Pressure Switch” (exhaust pressure switch) N.O.? If no, then check the hose and see if it
is filled with condensate.  If the hose is not filled with condensate, then replace pressure switch.
If filled empty hose.
Is the “Collector Limit Switch” N.C.? If no, then reset switch.  If this switch trips more than 3
times,  call service.
If all items above are ok, then replace the blower.

Is there voltage to the “Hot Surface Ignitor”?  Check for 120VAC to the ignitor from the ignition
module.
Is there continuity across the “Hot Surface Ignitor?” If no, then replace hot surface ignitor.  If
yes, then replace the ignition module.

Put your hand on the gas valve.  When the “Valve” LED lights on the ignition module, can you
feel it energize?  If not, then check the voltages at the ignition module across pins 2 and 7 on
the  plug “CONTROL”.  If there is 24 VAC across these pins, then check to see if the “Rectifier
Harness” is secure.  If it is secure, then replace the “Gas Valve”.
If you can feel the gas valve energize, check the main gas supply is not in the off position.

Is there minimum gas supplied to water heater as stated on the rating plate?  If not, then
increase the supply pressure to the water heater.
Measure the microAmps through the flame sensor using a multimeter.  Is there at least 4
microAmps?  If not, then replace the “Flame Sensor” or flame sensor wire.

Is the tank temperature above the temperature set point?
Does the T&P relief valve leak?   If yes, then replace “Thermostat PC Board.”

Check “Vacuum Switch” (air intake switch) as previously mentioned.
Check “Pressure Switch” (exhaust pressure switch) as previously mentioned.
Check “Collector Limit Switch” as previously mentioned.
If above switches are all ok, then replace “Ignition Module.”

TROUBLESHOOTING GUIDE

Main power light is not lit.

Thermostat does not call for heat.

Ignition module “Power” LED is not lit.

Blower does not energize.

Ignitor does not glow.

Main valve does not turn on.

Burner Flame keeps going out.

Thermostat does not satisfy.

Blower did not post purge

             

 9/07

 

Printed in USA

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: