background image

9

TNR-I&S-02

Through The Wall Venting with Low Ground Clearance:

When venting cannot exit through the wall at a height greater than or
equal to 12"

 (30.5 cm)

 (and above expected snow level) from the ground,

then the installation must be modified as shown below (see Figure 13).

Determining required vent length:

1. Determine the total length of straight vent pipe (in feet) required

for both the intake and the exhaust.

2. Add 5 feet of venting for every 90° elbow.

3. Add 2 ½ feet of venting for every 45° elbow.

4.

Total vent length can not exceed “Max Vent Length” in
Table 2.

5.

Air intake can not exceed exhaust by more than 30 feet in
any venting situation.

POWER VENT INSTALLATION

Power venting is where the indoor air is used and the exhaust is vented to
the outside.  Venting may be run horizontally through an outside wall or
vertically through a roof through using either 3 inch 

(7.6 cm)

 or 4 inch

(10.2 cm)

 diameter PVC or CPVC.  This water heater is supplied with a

screened intake and exhaust 90° elbow referred to as the exhaust vent
terminal and the air intake terminal.

Power Vent Terminal Location

Refer to the “Direct Vent Terminal Location” (see page 7) section
previously mentioned to determine the proper exhaust vent location.
Plan the vent system layout so that proper clearances are maintained
from plumbing and wiring. Vent pipes serving power vented appliances
are classified by building codes as “vent connectors”. Required
clearances from  combustible materials must be provided in accordance
with information in this manual under LOCATION OF WATER HEATER
and CLEARANCES, and with National Fuel Gas Code and local codes.

 

Figure 13

Vent Terminal (Low Ground Clearance)

NOTICE

DO NOT

 include the 3" exhaust elbow or vent terminals in

determining maximum vent length.

Table 2

Direct Vent Maximum Vent Length

Storage

Capacity

(Gallons)

Rated

Input

(BTU/HR)

Max Vent Length (ft)

3" PVC or CPVC

Max Vent Length (ft)

4" PVC or CPVC

6 0
6 0
6 0

1 0 0
1 0 0
1 0 0
1 0 0
1 0 0

125,000
150,000
199,000
150,000
199,999
250,000
300,000
399,999

1 2 0
1 0 0

8 0

1 2 0
1 0 0

8 0
6 0
5 0

1 7 0
1 5 0
1 3 0
1 7 0
1 5 0
1 3 0
1 1 0
1 0 0

 

Figure 12

Typical Vertical Direct Vent System Installation

Содержание TNR-I&S-02

Страница 1: ...perature and pressure relief valve complies with local codes If the combination temperature and pressure relief valve does not comply with local codes replace it with one that does Install a discharge...

Страница 2: ...ions will be short and direct 2 THIS WATER HEATER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR DO NOT install this water heater on carpeting 3 FOR BASEMENT INSTALLATION provide a solid level elev...

Страница 3: ...pening is to be located within twelve 12 inches of the enclosure top and the bottom opening within twelve 12 inches of the enclosure bottom Each opening shall have a free area of at least one square i...

Страница 4: ...the time it is open Keep clear of the combination temperature and pressure relief valve discharge line outlet The discharge may be hot enough to cause scald injury The water is under pressure and may...

Страница 5: ...injuy and may be used as a guide in determining the safest water temperature for your applications ALTERNATE SPACE HEATING WATER CONNECTIONS Connect the system supply and return piping to the water he...

Страница 6: ...on instructions Water heater must be protected from freezing downdrafts during shutdown periods Provide protection of the building materials from degradation by flue gases from the exhaust vent termin...

Страница 7: ...IONS FOR INSTALLATIONS The vent terminal must not terminate 1 Directly above a paved sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings 2 Less th...

Страница 8: ...de wall if vented on the same wall 2 Use the proper PVC cement to secure the 90 exhaust vent and air intake terminals provided with the water heater to the plastic pipes The distance between the back...

Страница 9: ...0 elbow referred to as the exhaust vent terminal and the air intake terminal Power Vent Terminal Location Refer to the Direct Vent Terminal Location see page 7 section previously mentioned to determin...

Страница 10: ...tical run and every 3 feet of horizontal run of vent pipe length Stress levels in the pipe and fittings can be significantly increased by improper installation If rigid pipe clamps are used to hold th...

Страница 11: ...other appliance Using this kit on other appliances and or water heaters can result in property damage personal injury or death DO NOT operate this water heater until the installation and assembly of t...

Страница 12: ...pipe See Figure 19 5 Install concentric Y fitting and pipe assembly through the structure s hole and field supplied roof boot flashing Do not allow insulation or other materials to accumulate inside p...

Страница 13: ...7 Take the time and effort to do a professional job Shortcuts will only cause you problems and delays in start up The majority of failures in these systems are the result of shortcuts and or improper...

Страница 14: ...any damage or injury caused as a result of a cracked gas inlet as a result of excessive torque This water heater and its gas connection must be leak tested before placing the water heater in operatio...

Страница 15: ...at satisfied 4 Blower pre purge 9 Main burner OFF 5 Igniter warm up 10 Blower post purge WARNING Water heaters are heat producing appliances To avoid damage or injury there must be no materials stored...

Страница 16: ...1 6 TNR I S 02 LIGHTING INSTRUCTIONS Figure 24 Lighting Instruction Label...

Страница 17: ...mperature during standby periods Lower water temperatures also extend tank life Remember no water heating system will provide exact temperatures at all times Allow a few days of operation at this sett...

Страница 18: ...em Condensate Line OPERATION Sediment Removal Inspect Check Operation Clean Inlet Screen Inspect Inspect Free of Shrubs Debris Inspect Inspect INTERVAL Monthly Semi Annually Semi Annually As Required...

Страница 19: ...sion Replace with a new valve of the recommended size as necessary A thorough inspection of the valve should be performed at least every three years by removing the temperature and relief valve from t...

Страница 20: ...illed with condensate then replace pressure switch If filled empty hose Is the Collector Limit Switch N C If no then reset switch If this switch trips more than 3 times call service If all items above...

Отзывы: