49
FIGURE 12.5
MONITOR SCREENS (ctd.)
SCREEN:
1 1
C a s c
D e s i g n
0
Shows the cascade address of the boiler 0 = MASTER, 1 ..... 11 = SLAVES
C a s I n f
0 1 2 3
4 5 6 7 8 9 A B
Displays number, priority and state of cascade boilers. (See below)
SCREEN:
1 2
C a s c
P o w e r
9 9 9 %
9 9 9 %
% heat demand of total (cascade) power available (% ).
D u a l
B u r n e r
:
N o
One heat exchanger equipped with two burners: "Yes" or "No".
SCREEN:
1 3
M a x
T h e r m
O p e n
Status of the maximum thermostat: "Open" or "Closed".
G e n
B l o c k
C l o s e d
Status of the general blocking contact: "Open" or "Closed".
SCREEN:
1 4
S i p h o n
p r e s s
C l o s e d
Status of the condensate drain pressure switch: "Open" or "Closed".
N R V
C o n t a c t
O p e n
Status of the non return valve contact: "Open" or "Closed".
Screen 11 "CASCINF" Description
The CasInf screen shows the number of boilers connected with the Cascade. The Master/Lead boiler is designated as 0. Slave/Lag boilers will be designated 1, 2, 3,
4, 5, 6, 7, 8, 9, A, B. When a “-“ is used instead of a number, than that boiler is either not connected, or in a lockout mode and not available for the Cascade. When an
“x“ is used instead of a number, than that boiler is connected, but in lockout mode.
When a “d” is used instead of a number, than that boiler is handling a DHW demand.
When the number is flashing, then that boiler is providing heat to the cascade. When the leading boiler is changed according to the set priority change time, then that
boiler’s address will be shown first in the row of numbers.
Example 1: "3 4 5 - - - - - - 0 1 2"
There are six boilers present and number 3 boiler has priority.
Example 2: "3 4 x - - - - - - d 1 2"
There are six boilers present and number 3 boiler has priority. Boiler 0 is heating up an indirect DHW tank. Boiler 5 is present, but in a lockout.
Содержание CP-M Series
Страница 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Страница 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Страница 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Страница 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Страница 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Страница 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Страница 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Страница 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Страница 94: ...94...