80
16.7
OTHER CHECKS
16.7.1
RELIEF VALVES (IF FITTED)
At least once a year, the pressure relief valve should be checked to ensure correct operation. To check the valve,
lift the lever or turn the screw cap at the end of the valve several times. The valve should operate freely and seat
properly.
If water does not flow, remove and inspect for obstructions or corrosion. Replace with a new valve of the
recommended size as necessary.
16.7.2
FLUE SYSTEM
Examine the exhaust and air intake system at least once a year. Points of inspection are as follows:
1.
Check for obstructions and/or deterioration of flue piping and terminal. Replace immediately where
needed.
2.
Check the terminal for any foreign material and remove as necessary.
3.
Check all flue system connections for leakage and reseal as required.
4.
Check that ventilation grilles comply with current regulations.