23
Once the mounting bracket is installed, the locking plate should be removed and the boiler should be fitted by lifting and tilting the
top rear edge back and hooking the mounting lip over the mounting bracket. With the boiler suspended, the locking plate should
be refitted and the boiler levelled using the bolts on the back of the appliance (see
Figure 6.1
).
FIGURE 6.1
LOCKING AND LEVELLING THE APPLIANCE
6.5
CONDENSATE DRAIN
The condensate drain is located in the centre of the boiler underside. The clean out bowl is supplied in a separate box within the
heater packaging; this must be fitted and the condensate water trap filled before the appliance is fired. The condensate trap is
fitted with a ¾” flexible hose that should be connected to an appropriate condensate drain, sloping continuously away from the
boiler at an angle of at least 3
(50mm per metre).
The Water Resources Act requires that trade effluent is discharged to municipal sewers between pH 6.5 and 10.0. If it is
determined that these levels cannot be achieved, an in-line condensate neutralisation kit is available as an ancillary option from
Lochinvar Limited. This unit is capable of neutralising 4000 litres of condensate to a pH of 7.0 before releasing it to a drain.
6.6
FILLING THE CONDENSATE TRAP
Prior to the appliance being put in to operation, the condensate water trap must be filled to prevent the escape of combustion
products. To fill the water trap, the bowl should be unscrewed from the boiler underside and filled with water to the top before re-
installing.
FIGURE 6.2
FILLING THE CONDENSATE TRAP
7.0
GAS SUPPLY
The Lochinvar CP-M+™ range is suitable for use on second and third family gasses 2H - G20 - 20mbar and 3P - G31 - 37mbar.
Details relating to Natural Gas (2H) appear below; for details relating to Propane (3P) please refer to
Section 15: LPG FUEL
.
7.1
SERVICE PIPES
The local gas distributor must be consulted at the installation planning stage in order to establish the availability of an adequate
supply of gas. An existing service pipe must not be used without prior consultation with the local gas distributor.
Содержание CP-M Series
Страница 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Страница 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Страница 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Страница 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Страница 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Страница 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Страница 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Страница 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Страница 94: ...94...