FIGURE 13.2
SETTING PARAMETERS (ctd.)
Menu A: Heating
A 7
H E
c P r b
3
2 5
o C
Menu A: Heating
A 8
H E
c l n t
3
8 0
S e c
Menu A: Heating
A 9
T i m e r C o n t
0
Menu B: Hot water
B 1
D H i p m p /
t w v
1
Menu B: Hot water
B 2
D H i
f
l o w
L O
2 5
o C
Menu B: Hot water
B 3
D H i
f
l o w
H I
8 5
o C
Menu B: Hot water
B 4
D H i
L O t
i m e
1
M i n
Menu B: Hot water
B 5
L e g i o
t e m p
8 5
o C
Menu B: Hot water
B 6
L e g i o
h y s t
2
o C
> > > From previous page < < <
> > > Continued on next page < < <
This parameter sets the Cascade CH proportional band. This is the temperature
range below the setpoint temperature in which each boiler in the cascade boiler
will modulate (as measured by the cascade sensor).
This parameter sets the cascade CH integration time. This is the time period over
which an average temperature is recorded in order to determine the firing rate (as
measured by the cascade sensor).
This parameter activates the external time control feature. When enabled, a
closed contact across terminals 13 & 14 runs the boiler at daytime temperatures,
an open contact runs the boiler at night-time temperatures. A value of 0 disables
this function, a value of 1 enables it.
This parameter sets how DHW production is controlled. A value of 0 is used
when a separate pump supplies the DHW vessel. A value of 1 is used when
the DHW supply is controlled by a 3-way valve.
This parameter sets the time period during which the DHW flow temperature will
be at the 'low level'. After this time period expires, the setpoint will automatically
switch to the 'high level.
This parameter sets the indirect DHW flow temperature from the boiler during a
DHW pasteurisation demand.
This parameter sets the differential during the pasteurisation function. This is the
temperature below the offset temperature which the boiler must reach before the
firing sequence will restart.
This parameter sets the 'low level' indirect DHW flow temperature from the boiler
during a DHW demand.
This parameter sets the 'high level' indirect DHW flow temperature from the boiler
during a DHW demand.
Содержание CP-M Series
Страница 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Страница 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Страница 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Страница 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Страница 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Страница 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Страница 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Страница 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Страница 94: ...94...