22
6.0
LOCATION
6.1
PLANT ROOM REQUIREMENTS
The Lochinvar CP-M+ may only be installed in a room that complies with the appropriate ventilation requirements.
The Lochinvar CP-M+ can be used as a type C
13
, C
33
C
43
, C
53
or C
83
appliance. Due to its room sealed design, ventilation
allowances for combustion air are not necessary. If the appliance is to be installed in a compartment or a hot environment,
ventilation for cooling purposes must be fitted. For further guidance, please refer to
Section 9
AIR SUPPLY
or to
BS6644
.
The Lochinvar CP-M+ can also be used as a type B
23
appliance. If such a configuration is to be used, then appropriate ventilation
for cooling and combustion must be provided. For further details, please refer to
Section 9
AIR SUPPLY
or to
BS6644
.
6.2
GENERAL REQUIREMENTS
Corrosion of the heat exchanger and flue system may occur if air for combustion contains certain chemical vapours. Such
corrosion may result in poor combustion and create a risk of severe personal injury or substantial property damage. Aerosol
propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium
chloride, waxes and process chemicals are corrosive. Products of this sort should not be stored near the boiler or outside by the
air intake (if applicable). The fitting of this equipment in a situation where aerosols or other chemicals may be entrained into the
combustion air will invalidate the warranty.
When using the boiler mounting frame, the equipment must be installed on a level surface that is capable of adequately
supporting the weight of the boiler(s), frame and any ancillary equipment. The operation of the equipment must not cause the
temperature of any combustible material in the vicinity of the equipment and its flue to exceed 65°C. If such a situation is
unavoidable, appropriate insulation should be provided. When mounting the boiler on a wall, investigations should be made as to
whether the wall is strong enough to support the full weight of the boiler and ancillary equipment.
Locate the equipment so that if the appliance or any connecting pipework should leak, water damage will not occur. When such
locations cannot be avoided it is recommended that a suitable drain pan be installed under the equipment. The pan should be
adequately drained but must not restrict the combustion or ventilation airflow.
6.3
CLEARANCES
The location chosen for the equipment must permit the provision for a satisfactory flue system and, where necessary, an
adequate air supply. The location must also provide adequate space for servicing and air circulation around each unit. This
includes any electrical trunking laid across the floor and to the appliance.
See
Figure 3.1
or
Figure 3.2
for dimensions/clearances. Further details regarding locations are given in
BS6644
.
6.4
MOUNTING THE BOILER
NOTE: The mounting bracket for the boiler is part of the shipping crate.
6.4.1
MOUNTING THE BOILER ON A FRAME
NOTE: Mounting frames are available for the suspension of one, two, three or four boilers.
When utilising the mounting frame, the assembly instructions supplied with the frame should be used.
A mounting bracket is supplied with the mounting frame. The locking plate should be removed and the frame positioned and
levelled in its required location before lifting any boiler in to place. With the boiler suspended on the frame, the locking plate
should be refitted and the boiler levelled using the bolts on the back of the appliance (see
Figure 6.1
).
6.4.2
MOUNTING THE BOILER ON THE WALL
A template is provided with the boiler showing the locations for the holes necessary for the mounting bracket. It is essential that
the mounting bracket is installed level using fixings that are strong enough to support the boiler and its ancillary equipment.
Содержание CP-M Series
Страница 5: ...5 2 0 PRINCIPAL PARTS FIGURE 2 1 REMOVABLE COMPONENTS CP M 60...
Страница 6: ...6 FIGURE 2 2 REMOVABLE COMPONENTS CP M 60 CONTINUED...
Страница 8: ...8 FIGURE 2 3 REMOVABLE COMPONENTS CP M 80 CP M 100...
Страница 9: ...9 FIGURE 2 4 REMOVABLE COMPONENTS CP M 80 CP M 100 CONTINUED...
Страница 11: ...11 FIGURE 2 5 REMOVABLE COMPONENTS CP M 120...
Страница 12: ...12 FIGURE 2 6 REMOVABLE COMPONENTS CP M 120 CONTINUED...
Страница 14: ...14 FIGURE 2 7 REMOVABLE COMPONENTS CP M 150 CP M 180...
Страница 15: ...15 FIGURE 2 8 REMOVABLE COMPONENTS CP M 150 CP M 180 CONTINUED...
Страница 94: ...94...