April 27, 2004 Manual Version 1.01
4.14
return, connect the strain gauges one at a time to determine which gauge causes
the shorted condition or verify that the resistance of each gauge (Vref to Gnd) is
approximately 350 ohms. If the problem remains, it indicates a failure on the
tonnage monitor analog board.
Section 4.4.3
Resetting Errors
If an alarm or error condition is detected, a stop signal is provided to the press control and a RESET
ERROR softkey provided in the Main Tonnage Monitor screen. If configured to lock out access to
resetting errors, this softkey will appear only with the RUN/PROG keyed selector switch in the PROG
position. In addition, if access codes have been enabled (see Section 2 for details), the operator will also
require an access code to reset the tonnage monitor.