Position window [0x01]
[Register 2, Unsigned16, rw]
This parameter defines the tolerance window limits for the
value. As soon as the axis is within the tolerance window limits,
When the axis is within the tolerance window limits for the time set in the
goes high (“=1”). The parameter is expressed in pulses. See
also the “Positioning: position and speed control” section on page 43.
Default = 1 (min. = 0, max. = 65535)
Position window time [0x02]
[Register 3, Unsigned16, rw]
It represents the time for which the axis has to be within the tolerance window
limits set in the
parameter before the state is signalled
through the
. The
parameter is expressed in milliseconds. See also the “Positioning: position and
speed control” section on page 43.
Default = 0 (min. = 0, max. = 10000)
Max following error [0x03-0x04]
[Registers 4-5, Unsigned32, rw]
This parameter defines the maximum allowable difference between the real
position and the theoretical position of the device. If the device detects a value
higher than the one set in this parameter, the
triggered and the unit stops. The parameter is expressed in pulses.
Default = 50000 (min. = 0, max. = 1000000)
Kp position loop [0x05]
[Register 6, Unsigned16, rw]
This parameter contains the proportional gain used by the PI controller for the
position loop. The value has been optimized by Lika Electronic according to the
technical characteristics of the device.
Default = 80 (min. = 0, max. = 1000)
Ki position loop [0x06]
[Register 7, Unsigned16, rw]
This parameter contains the integral gain used by the PI controller for the
position loop. The value has been optimized by Lika Electronic according to the
technical characteristics of the device.
Default = 10 (min. = 0, max. = 1000)
MAN RD6 MB E 1.1
Programming parameters
65 of 92
RD6 Modbus®