Lighthouse REMOTE Active Count Installation Guide
3-4
248083401-1 Rev 5
3. Even though the RJ-45 connectors used to build Ethernet cables are
typically the same for either end, the connector supplied in the kit
should be used on the instrument end.
4. If STP wire is needed, the RJ-45 required for wire termination is
metal-jacketed. This special RJ-45 provides a grounding point for
the cable’s shield. Only one end of the each cable should be
grounded, which will provide the shield to block electrical noise
from entering the wire but will not introduce a ground loop that
results from both ends being grounded. Because RS-485 hub have
grounded connector housings, the hub end should be used for this
ground connection.
Cable-build Procedure
Figure 3-1 shows the individual parts needed to assemble the Industrial
RJ-45 Cable connection.
Figure 3-1 Industrial RJ-45 Cable Parts
1. Remove the contents of the Industrial RJ-45 connector from the
package - do NOT dispose of or lose any pieces. Compare the
contents with Figure 3-1. Contact Lighthouse Support if it appears
that something is missing from the package or replacements are
needed.
2. Remove the large Lock Ring from the Housing if they are mated.
3. Loosen the small Cable Seal Nut to allow the CAT5e cable to pass
through.
RJ-45
Lock
RJ-45
Connector
CAT5e Cable
Lock
Ring
RJ-45 Housing
Wire
Loom
Seal
Cable Seal
Nut
Содержание REMOTE Active Count
Страница 1: ......
Страница 2: ...00...
Страница 6: ......
Страница 10: ...Lighthouse REMOTE Active Count Installation Guide ii 248083401 1 Rev 5...
Страница 12: ...Lighthouse REMOTE Active Count Operating Manual 1 2 248083401 1 Rev 5...
Страница 56: ...MODBUS Register Map v1 49 248083401 1 Rev 5 A 18...
Страница 58: ...Lighthouse REMOTE Active Count Installation Guide B 2 248083401 1 Rev 5...
Страница 61: ...00...
Страница 62: ......