Error Code
Description
Details
Space II Unit
2 4 1 Space II unit high pressure switch error.
System was turned off by the Space II unit high pressure switch.
2 6 1 Space II unit inverter compressor operation error.
Initial operation failure due to Space II unit inverter compressor
problem.
2 9 1 Space II unit inverter compressor overcurrent error.
Space II unit inverter compressor current draw is too high.
3 2 1 Excessive increase in Space II unit inverter compressor
gas discharge temperature.
•
Shutdown due to excessive discharge gas pressure.
•
Check flow switch, clean the strainer, and verify pump is
working properly.
3 4 1 Compressor high pressure safety tripped.
Shutdown due to excessive discharge gas pressure.
3 5 1 Low side pressure transducer senses pressure below
allowable limits.
Shutdown due to low suction pressure.
3 6 1 Space II unit low condensing ratio error.
Space II unit operating under the low condensing limit for 3
minutes.
3 9 1 Communication error between Space II unit PFC and
inverter board.
Space II unit inverter compressor current detection (CT) sensor
has disconnected or short circuited.
4 0 1 Space II unit inverter compressor current transducer
(CT) sensor error.
Space II unit inverter compressor current transducer (CT)detec-
tion sensor has disconnected or short circuited.
4 1 1 Space II unit inverter compressor discharge pipe tem-
perature sensor error.
•
Check the connection on the Space II unit PCB.
•
Thermistor has disconnected or short circuited.
4 2 1 Space II unit low pressure transducer error.
•
Check the connection on the Space II unit PCB.
•
Transducer has disconnected or short circuited.
4 3 1 Space II unit high pressure transducer error.
•
Check the connection on the Space unit PCB.
•
Transducer has disconnected or short circuited.
4 4 1 Space II unit ambient temperature sensor error.
•
Check the connection on the Space II unit PCB.
•
Thermistor has disconnected or short circuited.
4 6 1 Space II unit compressor suction pipe temperature
sensor error.
•
Check the connection on the Space II unit PCB.
•
Thermistor has disconnected or short circuited.
5 1 1 Combination ratio is out of range.
The total of the nominal indoor unit capacity is less than 50% or
more than 130% of the nominal Space II unit capacity.
5 2 1 Communication error between Space II unit main PCB
and inverter PCB.
•
Communication error between main PCB and inverter PCB.
•
Check connections at both sockets.
•
Inspect interconnecting cable for wear.
5 3 1 Communication error between Space II unit main PCB
and indoor unit(s) PCB.
•
Check if Space II unit to indoor unit(s) communications cable
has disconnected or short circuited.
•
Check A terminals are connected to indoor unit A and 3 (5 on 3
x 3 cassette) terminals; B connect to B or 4 (6 on 3 x 3
cassette) terminals.
6 0 1 Space II unit inverter PCB EPROM error.
•
Verify the EPROM is present and in the socket correctly.
•
Check if all pins are in and are not bent.
•
Check if notch in the chip lines up with the arrow on the socket.
6 2 1 High temperature at the Space II unit inverter heatsink. System shut off because of high temperatures at the Space II
unit inverter heatsink.
6 7 1 Space II unit fan has locked up.
Space II unit air flow is restricted.
7 1 1 Space II unit PFC current transducer (CT) sensor error. Space II unit PFC current transducer (CT) sensor has discon-
nected or short circuited.
7 3 1 Space II unit PFC instant overcurrent (peak) error.
Instant overcurrent (peak) of Space II unit PFC.
7 5 1 Space II unit fan CT sensor error.
Disconnection or short circuit of Space II unit fan current trans-
ducer (CT) sensor.
7 6 1 Space II unit fan DC link high voltage error.
Space II unit fan DC link high voltage error.
7 7 1 Space II unit fan overcurrent error.
Space II unit fan current is >10A (for 208-230V units).
7 8 1 Space II unit fan hall sensor error.
Space II unit fan hall sensor has disconnected or short circuited.
7 9 1 Space II unit fan operation failure error.
Space II unit fan is experiencing first position sensor failure.
For detailed information on how to troubleshoot each error, see the Space II Unit Service Manual on www.lg-vrf.com.
Table 30: Error Codes, continued.
Self Diagnosis Functions
electrIcal WIrInG