Additional screens can be accessed by tabs on the main screen.
Additional screens include the following:
1. Cycleview: Graphic of internal components including:
•
Compressors showing actual speeds
•
EEVs
•
IDUs
•
Temperature and pressure sensors
•
Four-way reversing valve
2. Graph: Full screen graph of actual high and low pressures and high
and low pressure limits. A sliding bar enables user to go back in
time and view data.
3. Control FTN: Enables user to turn on IDUs in 1.8°F increments.
4. Useful Tab
•
Unit Conversion: Converts metric values to imperial values.
•
Actual inverter compressor speed
•
Target inverter compressor speed
•
Actual outdoor fan speed
•
Target outdoor unit fan speed
•
Actual superheat
•
Target superheat
•
Actual subcooler circuit superheat
•
Target subcooler circuit superheat
•
Main EEV position
•
Subcooling EEV position
•
Inverter compressor current transducer value
•
Outdoor air temperature
•
Actual high pressure/saturation temperature
•
Actual low pressure/saturation temperature
•
Suction temperature
•
Inverter compressor discharge temperature
•
Front outdoor coil pipe temperature
•
Back outdoor coil pipe temperature
•
Liquid line pipe temperature
•
Subcooler inlet temperature
•
Subcooler outlet temperature
•
Average indoor unit (IDU) pipe temperature
•
Inverter compressor operation indicator light
•
Liquid injection
valves’ operation
indicator lights
•
Hot gas bypass
valve operation
indicator light
•
Four-way reversing
valve operation
indicator light
•
Pressure graph
showing actual low
pressure and high
pressure levels
•
Error code display
•
Operating mode
indicator
•
Target high pressure
•
Target low pressure
•
PCB (printed circuit board) version
•
Software version
•
Installer name
•
Model number of IDUs
•
Site name
•
Total number of connected IDUs
•
Communication indicators
•
IDU capacity
•
IDU operating mode
•
IDU fan speed
•
IDU EEV position
•
IDU room temperature
•
IDU inlet pipe temperature
•
IDU outlet pipe temperature
•
IDU error code
lG Monitoring View (lGMV) Diagnostic software
LGMV software (PRCTSL1 and PRCTFE1) allows the service technician or commissioning agent to connect a computer USB port to the
Space II unit main printed circuit board (PCB) using an accessory cable without the need for a separate interface device. The monitoring
screen for LGMV allows the user to view the following real time data on one screen:
Figure 63: MV Real-time Data Screen.
Figure 64: MV Cycleview.
Images on these pages are examples of LGMV screenshots. Actual images may differ depending on the version of the software and the units
installed.
Self Diagnosis Functions