Upload Central Control Address to the Indoor Units
For all ducted, vertical and floor standing indoor units, the central control address must be assigned using a wired zone controller. Wall-
mount, ceiling cassette, ceiling suspended, and the wall/ceiling convertible indoor units, the central control address can be assigned using a
wireless handheld controller or a wired zone controller.
Power Up All Indoor Unit PCBs
Turn the disconnect for each indoor unit to the “ON” position.
DO NOT
turn the unit ON (on/off button remains off).
Central Control Device
Maximum Indoor Unit Quantity
AC EZ
32
AC Smart II
64
AC Smart II with Expansion Kit
128
AC SMART Premium
128
LonWorks Gateway
64
BACnet Gateway
256
Advanced Control Platform
256
Table 28: Central Controller Indoor Unit Connection Limitations.
Central Controller Communications Limitations
Each type of Central Controller device is designed to communicate
with a limited quantity of indoor units. The quantity of indoor units
that can be connected to a single central control communications
cable, therefore, will be defined by the central control device on that
cable with the smallest Maximum Indoor Unit Quantity as shown at
right.
Group Number
If the building operator wants to know which indoor units are on each Space II unit, and multiple systems serve a building:
•
Assign a Group Number to each system. If there are more than 16 indoor units on a system, multiple Group Numbers may be necessary.
If the building owner wants to know which indoor units are on each floor:
•
Assign a different group number for each floor. If there are more than 16 indoor units on a floor, multiple Group Numbers may be
necessary.
Member Number
Can be assigned at will or for example, can follow the room layout on each floor.
For each LG Central Controller product provided on the project, devise a central control address schedule and assign a central control
address to each indoor unit(s) Hydro Kit(s), and ERV(s) units. Record this central control address for each component in the column provided
on the Pre-commissioning Device Configuration Worksheet.
Indoor Unit Central Control Address Assignments
A central control address is made up of two hexadecimal characters.
•
The first character in the central control address is the Hex Group Identifier.
Possible Hex Group Identifiers (in order of lowest to highest) are 0-9 followed by A-F.
•
The second character in the address is the Hex Member Identifier in a Hex Group.
Hex Member Identifiers (in order from lowest to highest) are 0-9 followed by A-F.
Figure 62: Central Control Address Nomenclature.
1
D
First character is
the Hex Group
Identifier 0-F
(Example: Group 1)
Second character
is the Hex Member
Identifier 0-F
(Example: Unit 14)
Hex Address Assignment Limitations
•
There is a limit of 16 Members per Hex Group
•
There is a limit of 16 Hex Groups per VRF system.
•
There is a limit of 256 possible Member Identifiers per Central Control
(See Central Controller Communications Limitations below).
Group Addressing