51
Electrical W
iring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Space II Unit DIP Switch Settings
electrIcal WIrInG
Check the Space II Unit Settings
It is possible to check the set values of the Space
II unit at the LED. (DIP switch settings should be
changed when the power is OFF.)
1. LED will display whether the DIP switch is
properly set.
Checking the Space II Unit Settings
Codes are displayed at the LED within five (5)
seconds after power is applied. The code
represents the set condition and model of the
Space II unit.
Model Code
→
Total Capacity
→
Model
Type
→
Normal
→
Model Name
1 ~ 255: Model Code
6 ~ 10 Horse Power: Total Capacity
2: Heat Pump Model
25: Normal
99: ARUN053GF2 Model
Example: ARUN053GF2
187 → 6 → 2 → 25 → 99
Setting the DIP Switches
•
If the DIP switches are set when the power is still ON, the new set-
ting will not be enabled immediately. The change only is enabled
when the power is cycled, or if the Reset button is pressed.
•
When executing the test operation, check the operating condition
of the indoor unit and only execute the test when all indoor units
have stopped operation.
•
Auto test operation will not work where only one indoor unit is
connected to the Space II unit.
•
Heat Pump model functions do not work on Cooling Only models.
Main PCB
LED
SW02V
(Auto Addressing)
SW01B
SW02B
Figure 57: Space II Unit Main PCB - DIP Switch Locations.
ON
OFF
ON
OFF
SW01B
SW02B
Figure 58: Space II Unit DIP Switches.
Function
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Increase Heating Capacity
●
X
IDU EEV Cool
● ●
●
●
X
IDU EEV Heat
● ●
● ●
SEER Mode (Ducted)
●
X
SEER Mode (Nonducted)
X
●
PCB Check
●
●
Control Box Check
●
●
IDU EEV Closing
X X
●
X X
IDU SC / SH Change
X X
X
●
X
IDU Minimum EEV
X
●
●
X X
Dry Contact
● ●
X
Snow Removal
●
X
Forced Defrost
X
●
Snow R Forced Defrost
● ●
Forced Overall Defrost
●
●
Static Pressure Compensation Mode 1
● ●
Static Pressure Compensation Mode 2
● ● ●
Static Pressure Mode 1
X X
● ●
X
X
Static Pressure Mode 2
● ● ●
● ●
Low Sound Operation
X
● ●
Night Low Sound Operation (Cooling
Only)
●
X
●
Night Low Sound Operation (Cooling /
Heating)
● ● ●
Static Pressure Change Mode
X
● ●
Pump Down
●
X
Pump Out
●
●
Forced Oil Return Operation
X X
●
X
Vacuum Mode
●
X X
●
Only Overall Defrost
●
Selector Fan / All Off
X X
● ●
X X
Space II Unit Address Setting
●
X X
Low Ambient
● ● ●
● = DIP Switch Set to ON
X = DIP Switch Set to OFF
Table 27: DIP Switch Settings Per Function.
If the applicable DIP switch is not set properly,
the system may not operate properly.
Содержание Multi V ARUN053GF2
Страница 1: ...Installation Manual Variable Refrigerant Flow Outdoor Unit 4 4 Tons ...
Страница 73: ......
Страница 74: ......