45
Electrical W
iring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure 48: Accessing the Power Wiring and Communi-
cation Cable Connections.
Capacity of Power Supply Wiring (current)
Recommended Minimum Distance
1,2
100V or more
10A
12 inches
50A
20 inches
100A
40 inches
Exceed 100A
60 inches
1
The figures above are based on parallel lengths up to 328 feet long. For lengths in excess of 328 feet, the distances will have to be recalculated in
direct proportion to the additional line lengths involved.
2
If the power supply waveform continues to exhibit some distortion, the space between the power wiring and communication cable should be increased.
•
Position the power wiring a minimum of two (2) inches away from the communication cables to avoid operation problems caused by electri-
cal interference. Do not run both in the same conduit.
•
If it is necessary to run the power wiring and communication cable alongside each other and cannot be avoided, see the table below for
minimum recommended distances.
Table 26: Power Wire and Communications Cable Minimum Required Separation Minimum Allowable Distances.
•
Do not secure the power wiring and communication cables together.
•
Do not run the power wiring and the communication cable in the same conduit.
separating Power Wires and communication cables
•
All power wiring and communication cable installation must be performed
by authorized service providers working in accordance with local, state, and
National Electrical Code regulations related to electrical equipment and wiring,
and following the instructions in this manual.
•
Undersized wiring may lead to unacceptable voltage at the unit and may cause
unit malfunction and be a fire hazard.
•
Properly ground the Space II unit and indoor units. Ground wiring is required
to prevent accidental electrical shock during current leakage, communication
problems from electrical noise, and motor current leakage. Ground wiring must
always be installed by a qualified technician.
Do not connect ground wire to refrig-
erant, gas, or water piping; to lightning rods; to telephone ground wiring; or to
the building plumbing system. Failure to properly provide an National Electri-
cal Code-approved earth ground can result in equipment malfunction, property
damage, electric shock, physical injury or death.
• Install appropriately sized breakers / fuses / overcurrent protection switches and wiring in accordance with local, state, and National
Electrical Code regulations related to electrical equipment and wiring, and following the instructions in this manual. Using an over-
sized breaker or fuse may result in equipment malfunction, property damage, electric shock, physical injury or death.
•
Consider ambient conditions (temperature, direct sunlight, inclement weather, etc.) when selecting, installing, and connecting the
power wiring.
•
If the system operates in reversed phase, it may damage the compressors and other components.
•
If there is a possibility of reversed phase, phase loss, momentary blackout, or the power goes on and off while the system is
operating, install a field-supplied phase loss protection circuit.
electrIcal WIrInG
General Information
Front Panel
DIRECTION OF PIPING/WIRING
To access the power wiring / communications cable
connections, remove all of the screws on the front
panel and pull it forward.