Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower tem-
perature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice:
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
- 51 -
Cycle Troubleshooting Guide
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
High
Defective compressor
Current is low.
Defective 4-way reverse valve
Normal
Excessive amount of
High pressure does not quickly
refrigerant
rise at the beginning of operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant(Leakage)
Clogging
Current is low.
Higher
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the rated
current
Temp. difference
: over 8°C
Temp. Difference
Operating Current
:
:
:
:
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage
Clog of refrigeration cycle
Defective compressor
Excessive amount of refrigerant
Normal