- 19 -
9. Soft Dry Operation.
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the operation
mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry operation, 5.5min operation OFF, 1.5min. only fan operation repeat. During
10min Dry operation, even if the room temperature falls below compressor OFF temperature, 10min(MAX)
Compressor ON from starting of Dry operation which includes 4 min. Compressor ON operation below the com-
pressor OFF temperature.
• In micom dehumidify mode, control of fan speed is as following.
ROOM TEMP.
Operation
Cooling
Dry operation
1.5 minutes
5.5 minutes
10 minutes
1 minutes
2 minutes
maximum
4 minutes
maximum
10 minutes
INDOOR FAN SPEED
ON
ON
ON
OFF
OFF
OFF
LOW
LOW
LOW
LOW
OFF
Selecting
fan speed
COMPRESSOR
SETTING TEMP.+1
°C
(COMP. ON)
SETTING TEMP.-0.5
°C
(COMP. OFF)
10. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
Cooling Model
Heat pump Model
Room Temp
≥
24°C
21°C
≤
Room Temp
24°C
Room Temp
21°C
Operation Mode
Cooling
Cooling
Soft Dry
Heating
Indoor Fan Speed
High
High
Low
High
Setting Temp.
22°C
22°C
Room Temp.
24°C