- 17 -
6.Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
For 9K, 12K Models
Intake Air temp.
Setting temp. +3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
Hot
Start
A
B
A
minimum
10sec.
minimum
10sec.
minimum
10sec.
OFF
COMPRESSOR
ON
OFF
ON
OFF
• A point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
• B point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
INDOOR FAN SPEED
LOW
OFF
LOW
LOW
OFF
7. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C. (BY TEMPERATURE)
• The operation diagram is as following.
PIPE
TEMP 28
°C
INDOOR
FAN SPEED
COMPRESSOR
ON
OFF
LOW
60 sec.
SELECTING
FAN SPEED
HOT-START BY TEMPERATURE