6. Indoor unit installation.
• Hook the indoor unit onto the upper portion of
installation plate. (Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.)
Ensure the hooks are properly seated on the instal-
lation plate by moving it in left and right.
7. Connecting the pipings to the indoor unit.
• Align the center of the pipings and sufficiently tight-
en the flare nut with fingers.
• Finally, tighten the flare nut with torque wrench until
the wrench clicks.
Wrench tightening the flare nut with torque wrench,
ensure the direction for tightening follows the
arrows on the wrench.
8. Wrap the insulation material around the
connecting portion.
- 29 -
Pipe Size
Torque
Liquid Side (1/4")
1.8kg.m
Gas Side (3/8")
4.2kg.m
Gas Side (1/2")
5.5kg.m
Connecting cable
Press the lower left and right side of the unit against the
Installation Plate until the hooks engages with their slots
(sound click).
Drain hose
Indoor unit
tubing
Flare nut Pipings
Spanner
Torque wrench
Plastic Bands
Installation material
Wrap the isulation material around the connecting
portion.