1. Time Delay Safety Control
• 3min... The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 2sec... The indoor fan is ceased for 2sec. to prevent relay noise.
(Protection of fan relay and micro chip)
• 30sec... The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode.
2. Airflow Direction Control
• This function is to swing the louver up and down automatically and to set it at the desired position.
• The procedure is as the following.
1st ;Press the ON/OFF Button to operate the product.
2nd ;Press the Airflow Direction Control Button to swing the louver up and down automatically.
3rd ;Repress the Airflow Direction Control Button to set the louver as the desired position.
3. Cooling Mode Operation
• When selecting the Cooling ( ) Mode Operation, the unit will operate according to the setting by the remote con-
troller and the operation diagram is as following.
4. Cooling or Heating Mode with Sleep Mode Auto Operation
• When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the
operation diagram is as following.
- 13 -
Operation Details
Operating Mode
Louver Position
Cooling
Start
2
Auto. Swing
1
~
4
Heating
Start
5
Auto. Swing
3
~
6
Selectig
fan speed
Intake Air temp.
More than
3 minutes
More than
3 minutes
Selecting
fan speed
Low
ON
OFF
ON
ON
OFF
Low
Selectin
fan speed
COMP. ON
(SET TEMP.+0.5°C
COMP. OFF
(SET TEMP.-0.5°C
INDOOR FAN SPEED
COMPRESSOR
(1) The function of main control