2) Vacuum pump maintenance
Because of their nature, most vacuum pumps contain large amounts of oil which lubricates bearings, etc., and functions
to enhance airtightness of pistons. When using a vacuum pump to discharge air from refrigerant piping, moisture in the
air tends to get mixed in with the oil. You must therefore change oil periodically and make sure the proper oil level is
maintained. (Perform periodic inspections in accordance with the operating instructions.)
3) Degree of vacuum measurement
An extremely accurate vacuum gauge is required to test degree of vacuum. You cannot accurately measure degree of
vacuum with the compound gauge on the gauge manifold. A Pirani vacuum gauge is required to measure degree of vac-
uum accurately. Because Pirani gauges are very sensitive and require extreme care when using, they are not very suit-
able for use in the field. You should therefore use the Pirani gauge to calibrate the attached vacuum gauge on the gauge
manifold and the degree of vacuum of the vacuum pump.
4) Calibration method
1. Connect a Pirani vacuum gauge and the gauge manifold vacuum gauge (760 mmHg) to the vacuum pump at the
same time, and run the pump for about 3 minutes.
2. Make sure the reading of the Pirani vacuum gauge is 5 Torr or less. The reading of conventional vacuum pumps low-
ers to about 0.2 Torr.
If the reading is not 5 Torr or less, check the vacuum pump oil. (Oil is low in many cases.)
3. Check the attached gauge on the gauge manifold. Adjust the gauge if the reading is not exactly correct.
4. Adjust the gauge manifold valve so that the Pirani vacuum gauge reads 5 Torr.
5. Mark the position indicated by the gauge manifold gauge with an oil based ink pen.
6. Use the mark of the gauge manifold as a target when vacuuming in the field.
Pressure detection section
Indicator
Vacuum pump
Gauge manifold
(Reference) Types of vacuum pump with respect to maximum degree of vacuum
Type
Maximum degree of vacuum
Use
Expulsion capacity Vacuum drying Air expulsion
Oil rotary
(Oil using)
0.02 mmHg
100
ℓ
/min(3.53 ft
3
/min)
10 mmHg
50
ℓ
/min(1.77 ft
3
/min)
0.02 mmHg
40
ℓ
/min(1.41 ft
3
/min)
Suitable
Suitable
Oilless rotary
(No need of oil)
Unsuitable
Suitable
Suitable
Suitable
Many handy
pumps fall into this
category
2. Guideline for each installation process
Heat pump 60Hz/R410A
_
33
Installation of
Outdoor Units
SINGLE ZONE
Содержание ATNH24GPLE2
Страница 1: ...SINGLE ZONE Heat pump 60Hz R410A 6CSL0 01B Replaces 6CSL0 01A ...
Страница 2: ...SINGLE ZONE General Information Indoor Units Outdoor Units Design and installation ...
Страница 5: ...SINGLE ZONE Part 1 General information 1 Model Line up 2 Nomenclature 3 Individual Control System ...
Страница 9: ...SINGLE ZONE Part 2 Product data n Indoor units n Outdoor units ...
Страница 14: ...Indoor Units 4 _ Heat pump 60Hz R410A 1 Ceiling cassette 4 way SINGLE ZONE TM Chassis ATNH42GMLE2 LCN427HV ...
Страница 26: ...Outdoor Units 6 _ Heat pump 60Hz R410A 1 DC Inverter SINGLE ZONE SINGLE ZONE U3 Chassis AUUW42GD2 LUU427HV ...