Outdoor Units
Heat pump 60Hz/R410A
_
1
1. DC Inverter SINGLE ZONE
SINGLE ZONE
1.1 Power supply
External wiring procedure
- The power supply work is needed only to the outdoor unit. The power supply to the BD unit and the indoor unit is
conducted through the communication wiring. Therefore, the power supply work can be carried out at just one place of the
outdoor unit. It will simplify the work procedure and save cost.
- Wiring cable size must comply with the applicable local and national codes.
Circuit breaker
Earth
Power supply
Outdoor unit
Type
Outdoor unit
Capacity (kBtu/h)
Circuit breaker
capacity
Power supply
Voltage range
1Phase
Inverter
AUUW24GD2 [LUU247HV]
24.0
30A
208/230V, 1Ø, 60Hz
MIN.:187
MAX.:253
AUUW42GD2 [LUU427HV]
42.0
40A