Outdoor Units
Heat pump 60Hz/R410A
_
9
1. DC Inverter SINGLE ZONE
1.7 Capacity tables
Models : AUUW24GD2 [LUU247HV] + ATNH24GPLE2 [LCN247HV]
• Cooling Capacity
• Heating Capacity
• Symbol
DB : Dry bulb temperature [°F]
WB : Wet bulb temperature [°F]
TC : Total capacity [kBtu/h]
SHC : Sensible capacity [kBtu/h]
PI : Power Input [kW]
(Comp.+ indoor fan motor+outdoor fan motor)
• Notes
1. All capacities are net. A deduction (cooling mode) or an
addition (heating mode) of Capacity due to operating
heat of indoor unit motor is reflected.
2.
indicates rated capacity at the standard
temperature condition.
- Heating mode Outdoor conditions : 85%RH.
However, the condition on nominal capacity is
7°CDB/6°CWB(44.6°FDB/42.8°FWB)
3. Direct interpolation is permissible. Do not extrapolate.
4. Capacities are based on the following conditions:
- Interconnecting Piping Length : 7.6m(25ft)
- Level Difference : Zero.
SINGLE ZONE
Outdoor Air
Temperature
Indoor Air Temperature : °FDB / °FWB
68.0 / 57.2
71.6 / 60.8
77.0 / 64.4
80.6 / 66.2
86.0 / 71.6
89.6 / 75.2
°FDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
68.0
23.53 19.68
1.05
24.98 19.94
1.43
26.43 20.11
1.55
27.15 20.29
1.56
29.33 20.70
1.56
30.78 21.08
1.55
77.0
22.51 19.05
1.10
23.95 19.34
1.44
25.39 19.55
1.56
26.11 19.74
1.58
28.28 20.18
1.61
29.72 20.59
1.62
89.6
21.13 18.28
1.48
22.57 18.63
1.75
24.00 18.89
1.83
24.72 19.10
1.85
26.87 19.61
1.90
28.31 20.05
1.93
95.0
20.49 17.66
1.65
21.92 18.03
1.87
23.35 18.31
1.94
24.00 18.48
1.91
26.20 19.05
2.00
27.63 19.50
2.04
104.0
19.59 17.12
1.81
21.02 17.53
1.95
22.45 17.85
1.98
23.16 18.08
1.99
25.30 18.66
2.02
26.73 19.13
2.06
109.4
19.05 16.52
1.78
20.48 16.95
1.86
21.91 17.28
1.86
22.62 17.52
1.85
24.76 18.11
1.87
26.19 18.60
1.91
114.8
18.51 16.01
1.59
19.94 16.46
1.61
21.37 16.81
1.58
22.08 17.06
1.56
24.22 17.67
1.56
25.65 18.16
1.60
118.4
17.43 15.23
1.37
18.80 15.68
1.35
20.17 16.04
1.28
20.85 16.28
1.26
22.91 16.89
1.25
24.28 17.37
1.28
Outdoor Air
Temperature
Indoor Air Temperature : °FDB
60.8
64.4
68.0
69.8
71.6
75.2
°FWB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-0.4
19.99
2.14
19.65
2.16
19.40
2.18
19.30
2.20
19.22
2.21
18.92
2.26
5.0
20.30
2.12
20.10
2.15
19.96
2.19
19.91
2.21
19.88
2.24
19.64
2.29
14.0
21.36
2.07
21.33
2.12
21.32
2.17
21.32
2.20
21.32
2.23
21.12
2.30
23.0
23.15
2.16
23.18
2.23
23.19
2.29
23.19
2.32
23.18
2.36
22.90
2.42
32.0
24.73
2.33
24.71
2.39
24.65
2.45
24.60
2.49
24.53
2.52
24.33
2.58
42.8
27.45
2.49
27.27
2.55
27.00
2.60
26.83
2.62
26.63
2.65
26.42
2.69
50.0
29.00
2.59
28.64
2.64
28.45
2.68
28.45
2.70
28.41
2.71
27.94
2.74
59.0
31.47
2.76
31.37
2.79
31.43
2.81
31.22
2.81
30.96
2.81
30.61
2.83
64.4
32.94
2.85
32.52
2.86
32.22
2.86
31.80
2.85
31.32
2.84
30.47
2.83
Содержание ATNH24GPLE2
Страница 1: ...SINGLE ZONE Heat pump 60Hz R410A 6CSL0 01B Replaces 6CSL0 01A ...
Страница 2: ...SINGLE ZONE General Information Indoor Units Outdoor Units Design and installation ...
Страница 5: ...SINGLE ZONE Part 1 General information 1 Model Line up 2 Nomenclature 3 Individual Control System ...
Страница 9: ...SINGLE ZONE Part 2 Product data n Indoor units n Outdoor units ...
Страница 14: ...Indoor Units 4 _ Heat pump 60Hz R410A 1 Ceiling cassette 4 way SINGLE ZONE TM Chassis ATNH42GMLE2 LCN427HV ...
Страница 26: ...Outdoor Units 6 _ Heat pump 60Hz R410A 1 DC Inverter SINGLE ZONE SINGLE ZONE U3 Chassis AUUW42GD2 LUU427HV ...