3. Installation of indoor unit
• Countermeasure:
- Use the carpet on the floor (compared to the tiles the car-
pet over it will have a 3 degree rise in temperature)
- Insulating the floor.
- Floor heating
3) In case of high temperature or high humid-
ity between the false ceiling and ceiling
slab(near by the sea, river, lake, spa)
• In case of temperature of 30 degree and humidity
above 80%, the units body as well as the piping
insulation should be strengthened.
Refer to the picture given below.
• Places having the temperature and humidity of the
surrounding and the
The surrounding water sources(sea, river etc.)
In case the steam is generated between the false ceiling
and the ceiling slab
Due to some nearby by steam source.
- Indoor unit: Insulate the unit body with some insulation
like glass wool atleast 10(3/8)mm(inch) in thickness.
• In case of the multi flow type, use the high humidity kit.
Otherwise the dew drops can be seen in the unit body.
• Refrigerant piping: Increase the piping insulation
thickness with thickness above 20(25/32)mm(inch).
• Others: Inside the ceiling near th air tight seal places
(no escape of the humidity)
• In case of multiple indoor cassette units
(recommended)
• Case of cold air intake:
The duct surface will have the dew drops so a insula-
tion on the duct is a must.(Insulation material: a glass
wool of thickness 25(31/32)mm(inch) will be appropri-
ate.)
CAUTION
30℃(86℉)
Psychrometric chart
Enhance additional
insulation required area
Relative humidity
Additional insulation required
Refrigerant piping
Grill for ventilation
Above
1500(59-1/6)
mm(inch)
Indoor unit
Lighting
Ventilator
Indoor unit
Above 2000(78-23/32 )mm(inch)
Above 3000(118-3/32 )mm(inch)
40
_
Heat pump 60Hz/R410A
Installation of
Outdoor Units
SINGLE ZONE
Содержание ATNH24GPLE2
Страница 1: ...SINGLE ZONE Heat pump 60Hz R410A 6CSL0 01B Replaces 6CSL0 01A ...
Страница 2: ...SINGLE ZONE General Information Indoor Units Outdoor Units Design and installation ...
Страница 5: ...SINGLE ZONE Part 1 General information 1 Model Line up 2 Nomenclature 3 Individual Control System ...
Страница 9: ...SINGLE ZONE Part 2 Product data n Indoor units n Outdoor units ...
Страница 14: ...Indoor Units 4 _ Heat pump 60Hz R410A 1 Ceiling cassette 4 way SINGLE ZONE TM Chassis ATNH42GMLE2 LCN427HV ...
Страница 26: ...Outdoor Units 6 _ Heat pump 60Hz R410A 1 DC Inverter SINGLE ZONE SINGLE ZONE U3 Chassis AUUW42GD2 LUU427HV ...