98 | HIGH STATIC
MUL
TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Cooling Capacity Tables
DUCTED HIGH STATIC
ARNU963B8A4
Table 61: ARNU963B8A4 Cooling Capacity Table.
Model No./
Capacity Index
Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F DB / WB)
68 / 57
73 / 61
79 / 64
80 / 67
85 / 70
88 / 73
91 / 76
TC
SHC TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
ARNU963B8A4/
95.9
-9.9
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
-5
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
0
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
5
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
10
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
14
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
20
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
23
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
25
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
30
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
35
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
40
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
45
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
50
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
55
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
123.9 71.3
60
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
122.7 70.9
65
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
120.7 69.8
70
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
119.1 68.6
75
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
114.3 71.3
115.9 67.1
80
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 107.5 72.0
111.1 70.9
113.1 66.8
85
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 106.3 71.3
107.5 67.9
109.5 64.1
90
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 104.7 70.1
105.5 66.8
107.5 63.4
95
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 102.7 69.8
104.7 66.4
106.3 62.6
100
63.1
51.3 76.7 59.2
86.3 63.0
95.9
67.1 100.7 68.6
102.7 65.6
104.7 62.2
105
63.1
51.3 72.7 56.2
82.3 60.3
91.9
64.1 95.6
64.1
98.7
63.4
101.5 60.7
110
61.5
49.8 69.1 53.2
76.7 56.2
86.3
60.3 90.3
60.3
93.9
60.3
97.9
58.8
115
60.0
48.3 65.7 50.5
72.1 52.8
81.1
57.3 84.9
57.3
89.2
57.3
94.0
56.5
118
58.5
46.9 62.3 47.9
68.5 49.7
77.9
54.4 81.0
54.4
85.2
54.4
90.2
54.2
122
57.0
45.4 59.3 45.5
64.7 46.7
73.7
51.7 76.7
51.7
80.6
51.7
86.6
51.7
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Cooling range with the Low Ambient Baffle Kit (sold separately) installed on the outdoor
unit(s) is -9.9°F to +122°F, and is achieved only when all indoor units are operating in
cooling mode. Does not impact heat recovery system synchronous operating range.
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.