VAH | 173
Vertical / Horizontal
Air Handler
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Cooling Capacity Tables
ARNU123NJA4
VERTICAL / HORIZONTAL AIR HANDLER
Model No./
Capacity Index
Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F DB / WB)
68 / 57
73 / 61
79 / 64
80 / 67
85 / 70
88 / 73
91 / 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
ARNU123NJA4/
12.0
-9.9
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
-5
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
0
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
5
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
10
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
14
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
20
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
23
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
25
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
30
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
35
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
40
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
45
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
50
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
55
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.5 10.8
60
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.4 10.8
65
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 15.1 10.6
70
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 14.9 10.4
75
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 14.3 10.8 14.5 10.2
80
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.5 10.9 13.9 10.8 14.2 10.1
85
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.3 10.8 13.5 10.3 13.7 9.7
90
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 13.1 10.7 13.2 10.1 13.5 9.6
95
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 12.9 10.6 13.1 10.1 13.3 9.5
100
7.9 7.8 9.6 9.0 10.8 9.6 12.0 10.2 12.6 10.4 12.9 10.0 13.1 9.5
105
7.9 7.8 9.1 8.5 10.3 9.2 11.5 9.7 12.0 9.7 12.4 9.6 12.7 9.2
110
7.7 7.6 8.7 8.1 9.6 8.5 10.8 9.2 11.3 9.2 11.8 9.2 12.3 8.9
115
7.5 7.3 8.2 7.7 9.0 8.0 10.2 8.7 10.6 8.7 11.2 8.7 11.8 8.6
118
7.3 7.1 7.8 7.3 8.6 7.5 9.7 8.3 10.1 8.3 10.7 8.3 11.3 8.2
122
7.1 6.9 7.4 6.9 8.1 7.1 9.2 7.9 9.6 7.9 10.1 7.9 10.8 7.9
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
Table 131: ARNU123NJA4 Cooling Capacity Table.
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Cooling range with the Low Ambient Baffle Kit (sold separately) installed on the outdoor
unit(s) is -9.9°F to +122°F, and is achieved only when all indoor units are operating in
cooling mode. Does not impact heat recovery system synchronous operating range.
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.