HIGH STATIC | 17
Ducted High Static
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
DUCTED HIGH STATIC
Electrical Data
Table 6: Ducted High Static Indoor Unit Electrical Data.
Model
Voltage Range
MCA
MOP
Rated
Amps
(A)
Power Supply
Power Input (W)
Hz
Volts
Phase
Max.
Cooling
Max.
Heating
L / M / H at
Factory Default
BH Units
ARNU073BHA4
208-230
1.32
15
1.06
60
208-230
1
150
150
49 / 52 / 58
ARNU093BHA4
1.32
1.06
150
150
52 / 58 / 67
ARNU123BHA4
1.32
1.06
150
150
58 / 67 / 78
ARNU153BHA4
1.32
1.06
150
150
58 / 78 / 90
ARNU183BHA4
1.32
1.06
150
150
78 / 90 / 103
ARNU243BHA4
1.32
1.06
150
150
103 / 117 / 132
M2 Units
ARNU073M2A4
208-230
2.9
15
2.3
60
208-230
1
430
430
21 / 29 / 38
ARNU093M2A4
2.9
2.3
430
430
21 / 29 / 38
ARNU123M2A4
2.9
2.3
430
430
25 / 34 / 43
ARNU153M2A4
2.9
2.3
430
430
25 / 34 / 43
ARNU183M2A4
2.9
2.3
430
430
34 / 43 / 67
ARNU243M2A4
2.9
2.3
430
430
34 / 43 / 67
ARNU283M2A4
2.9
2.3
430
430
57 / 88 / 123
ARNU363M2A4
2.9
2.3
430
430
88 / 123 / 184
ARNU423M2A4
2.9
2.3
430
430
136 / 193 / 231
M3 Units
ARNU283M3A4
208-230
3.1
15
2.5
60
208-230
1
650
650
60 / 83 / 109
ARNU363M3A4
3.1
2.5
650
650
75 / 107 / 161
ARNU423M3A4
3.1
2.5
650
650
75 / 107 / 161
ARNU483M3A4
3.1
2.5
650
650
75 / 107 / 172
ARNU543M3A4
3.1
2.5
650
650
172 / 215 / 260
B8 Units
ARNU363B8A4
208-230
6.5
15
5.2
60
208-230
1
800
800
403 / 420 / 478
ARNU423B8A4
6.5
5.2
800
800
465 / 497 / 528
ARNU483B8A4
6.5
5.2
800
800
482 / 500 / 538
ARNU763B8A4
6.5
5.2
800
800
505 / 505 / 765
ARNU963B8A4
6.5
5.2
800
800
750 / 750 / 800
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use the circuit breaker.
M
ax. power input is rated at maximum setting value.