42 | HIGH STATIC
MUL
TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Model
Capacity (MBh)
Mode
Setting Value Standard ESP (in. wg) CFM
Min. ESP (in.
wg)
Max. ESP (in.
wg)
ARNU363B8A4
36.2
High
(Factory Set)
High
92
0.70
1,730
0.35
0.98
Mid
88
1,317
Low
84
1.067
Standard
High
74
0.35
1,896
0.35
0.98
Mid
70
1,748
Low
66
1,550
ARNU423B8A4
42.0
High
(Factory Set)
High
93
0.70
1,914
0.35
0.98
Mid
89
1,459
Low
85
1,123
Standard
High
75
0.35
1,964
0.35
0.98
Mid
71
1,787
Low
66
1,589
ARNU483B8A4
48.1
High
(Factory Set)
High
94
0.70
2,020
0.35
0.98
Mid
90
1,519
Low
86
1,201
Standard
High
76
0.35
2,048
0.35
0.98
Mid
71
1,847
Low
67
1,670
ARNU763B8A4
76.4
High
(Factory Set)
High
102
0.86
2,119
0.47
0.98
Mid
98
1,766
Low
98
1,766
Standard
High
86
0.59
2,260
0.47
0.98
Mid
83
1,766
Low
83
1,766
ARNU963B8A4
95.9
High
(Factory Set)
High
105
0.86
2,542
0.47
0.98
Mid
102
2,260
Low
102
2,260
Standard
High
94
0.59
2,684
0.47
0.98
Mid
89
2,260
Low
89
2,260
Table 28: B8 Unit External Static Pressure Ranges.
The table above show the available E.S.P. range.
DUCTED HIGH STATIC
External Static Pressure Ranges
B8 Units