HIGH STATIC | 123
Ducted High Static
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Heating Capacity Tables
DUCTED HIGH STATIC
ARNU963B8A4
Table 86: ARNU963B8A4 Heating Capacity Table.
Model No./
Capacity Index
Outdoor
Air Temp.
Indoor Air Temperature (°F DB)
59
61
64
67
70
73
76
80
°F DB °F WB
TC
TC
TC
TC
TC
TC
TC
TC
ARNU963B8A4/
95.9
-21.6
-22.0
54.5
54.5
54.5
54.5
53.8
53.8
53.8
53.8
-17.1
-17.5
61.1
61.1
61.1
61.1
60.3
60.3
60.3
60.3
-12.6
-13
67.7
67.7
67.7
67.7
66.8
66.8
66.8
66.8
-7
-7.6
69.9
69.9
69.9
69.9
68.8
68.8
68.8
68.8
-4
-4.4
72.0
72.0
72.0
72.0
71.0
71.0
71.0
71.0
0
-0.4
74.2
74.2
74.2
74.2
74.2
73.1
73.1
73.1
5
4.5
83.9
82.8
81.7
81.7
81.7
81.7
81.7
81.7
10
9
87.1
87.1
87.1
86.0
86.0
86.0
86.0
86.0
15
14
92.5
92.5
92.5
92.5
92.5
92.5
91.4
90.3
20
19
97.8
97.8
97.8
97.8
95.7
95.7
94.1
93.0
25
23
102.1 102.1
102.1
102.1
102.1
100.0
98.9
94.1
30
28
104.3 104.3
104.3
104.3
104.3
102.1
98.9
94.1
35
32
107.5 107.5
107.5
107.5
106.4
104.3
98.9
94.1
40
36
111.8
111.8
111.8
111.8
107.5
104.3
98.9
94.1
45
41
116.1 116.1
116.1
112.9
107.5
104.3
98.9
94.1
47
43
120.4 119.3
118.3
112.9
107.5
104.3
98.9
94.1
50
46
129.0 123.6
118.3
112.9
107.5
104.3
98.9
94.1
55
51
131.7 124.7
118.3
112.9
107.5
104.3
98.9
94.1
60
56
131.7 124.7
118.3
112.9
107.5
104.3
98.9
94.1
TC: Total Capacity (MBh).
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.