38 | HIGH STATIC
MUL
TI V Ducted Indoor Unit Engineering Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
External Static Pressure Ranges
DUCTED HIGH STATIC
BH Units
Table 24: BH Unit External Static Pressure Ranges.
Model
Capacity (MBh)
Mode
Setting Value Standard ESP (in. wg) CFM Min. ESP (in. wg) Max. ESP (in. wg)
ARNU073BHA4
7.5
High
(Factory Set)
Hl
120
0.31
230
0.23
0.47
Mid
117
205
Low
115
191
Standard
Hl
110
0.23
258
0.15
0.31
Mid
107
222
Low
105
198
ARNU093BHA4
9.6
High
(Factory Set)
Hl
125
0.31
286
0.23
0.47
Mid
120
230
Low
117
205
Standard
Hl
110
0.23
258
0.15
0.31
Mid
107
222
Low
105
198
ARNU123BHA4
12.3
High
(Factory Set)
Hl
130
0.31
339
0.23
0.47
Mid
125
286
Low
120
230
Standard
Hl
115
0.23
307
0.15
0.31
Mid
110
258
Low
105
198
ARNU153BHA4
15.4
High
(Factory Set)
Hl
135
0.31
399
0.23
0.47
Mid
130
339
Low
120
230
Standard
Hl
123
0.23
388
0.15
0.31
Mid
120
357
Low
115
307
ARNU183BHA4
19.1
High
(Factory Set)
HI
140
0.31
459
0.23
0.47
Mid
135
399
Low
130
339
Standard
HI
130
0.23
466
0.15
0.31
Mid
125
413
Low
110
258
ARNU243BHA4
24.2
High
(Factory Set)
HI
150
0.31
565
0.23
0.47
Mid
145
509
Low
140
459
Standard
HI
145
0.23
618
0.15
0.31
Mid
135
519
Low
128
445
The table above shows the available E.S.P. range.