LOW STATIC | 143
Ducted Low Static
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Cooling Capacity Tables
DUCTED LOW STATIC
Table 106: ARNU123L2G4 Cooling Capacity Table.
ARNU123L2G4
Model No./
Capacity Index
Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F DB / WB)
68 / 57
73 / 61
79 / 64
80 / 67
85 / 70
88 / 73
91 / 76
TC
SHC TC SHC TC SHC TC SHC
TC
SHC
TC
SHC
TC
SHC
ARNU123L2G4/
12.3
-9.9
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
-5
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
0
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
5
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
10
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
14
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
20
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
23
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
25
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
30
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
35
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
40
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
45
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
50
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
55
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.9
9.5
60
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.7
9.4
65
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.5
9.3
70
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
15.3
9.1
75
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.7
9.5
14.9
8.9
80
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.8
9.6
14.2
9.4
14.5
8.9
85
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.6
9.5
13.8
9.0
14.0
8.5
90
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.4
9.3
13.5
8.9
13.8
8.4
95
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
13.2
9.3
13.4
8.8
13.6
8.3
100
8.1
6.8
9.8 7.9 11.1
8.4
12.3
8.9
12.9
9.1
13.2
8.7
13.4
8.3
105
8.1
6.8
9.3 7.5 10.6
8.0
11.8
8.5
12.3
8.5
12.7
8.4
13.0
8.1
110
7.9
6.6
8.9 7.1
9.8
7.5
11.1
8.0
11.6
8.0
12.0
8.0
12.6
7.8
115
7.7
6.4
8.4 6.7
9.2
7.0
10.4
7.6
10.9
7.6
11.4
7.6
12.1
7.5
118
7.5
6.2
8.0 6.4
8.8
6.6
10.0
7.2
10.4
7.2
10.9
7.2
11.6
7.2
122
7.3
6.0
7.6 6.0
8.3
6.2
9.4
6.9
9.8
6.9
10.3
6.9
11.1
6.9
Low ambient performance with LGRED° heat technology is included in Multi V 5 Air Source Units produced after February 2019.
TC: Total Capacity (MBh); SHC: Sensible Heat Capacity (MBh).
Cooling range with the Low Ambient Baffle Kit (sold separately) installed on the outdoor
unit(s) is -9.9°F to +122°F, and is achieved only when all indoor units are operating in
cooling mode. Does not impact heat recovery system synchronous operating range.
The System Combination Ratio must be between 50–130%.
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change
without notice.
Current certified ratings are available at
www.ahridirectory.org
.
For outdoor unit performance data, see the respective outdoor unit performance data
manuals on
https://lghvac.com/commercial
.