Ducted High Static
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 21: M3 Unit External Static Pressure and Air Flow Table.
1. All static pressure air flow rates are listed in CFM.
2. The tables above show the correlation between air flow rates and external static pressure.
3. The tables above show the available external static pressure range.
If the external static pressure of the installed indoor unit is less than the lowest value (as mentioned in the table), the indoor unit components can fail.
External Static Pressure and Air Flow Tables
DUCTED HIGH STATIC
M2, M3 Units
Table 22: ARNU283~423M2A4 External Static Pressure and Air Flow Table.
ARNU283~423M2A4 External Static Pressure and Air Flow Table.
M2 Unit External Static Pressure and Air Flow Table.
Set value
Static Pressure (in wg)
0.16
0.24
0.31
0.39
0.47
0.55
0.63
0.71
Air Flow Rate[CFM]
90
812
95
914
676
100
1010
823
105
1110
931
691
110
1208
1056
854
115
1292
1153
1016
765
120
1383
1260
1121
926
692
125
1473
1358
1227
1087
857
130
1554
1456
1332
1203
1023
787
135
1545
1437
1318
1150
971
723
140
1534
1426
1313
1151
909
701
145
1533
1468
1320
1084
868
150
1532
1493
1249
1036
155
1543
1324
1155
ARNU283~543M3A4 External Static Pressure and Air Flow Table.
M3 Unit External Static Pressure and Air Flow Table.
Set value
Static Pressure (in wg)
0.16
0.24
0.31
0.39
0.47
0.55
0.63
0.71
0.79
Air Flow Rate [CFM]
70
891
75
1074
756
80
1235
959
654
85
1404
1250
869
90
1562
1416
1111
800
95
1741
1581
1300
1017
754
100
1872
1744
1574
1251
978
105
2020
1910
1737
1518
1234
935
110
2076
1903
1691
1497
1193
858
522
115
2069
1867
1687
1500
1108
717
646
120
2040
1874
1701
1384
1066
868
125
1913
1744
1520
1296
1168
130
1927
1860
1714
1567
1398
135
1772
1596