Page 20
Step-by-step Mounting
Step 1:
Locate where the cabinet will be hung on the wall.
Choose a location in a dry area that is convenient to
the branch circuit panel.
Step 2:
Leviton requires that cabinet mounting hardware
reach through the drywall to wall studs or other
suitable solid backing. However, properly sized struts
and suitable hardware can be used. They must
distribute the load to the anchors without exceeding
the recommended anchor limit. Using drywall
screws directly through drywall without a stud is not
acceptable. Make sure that there is adequate
support.
Step 3:
Remove the cover. Some cabinets may require the
removal of data and/or grounding wires. Make sure
that this occurs prior to removal of the door and that
they are reconnected when reinstalling the door. On
cabinets with hinges, simply lift the door off the
hinges. On cabinets with screws, remove the cover
screws. Appropriately store the cover for future use.
Step 4:
On the (4) relay remote relay panel only, locate the
mounting plate assembly attached to the back of the
enclosure. Locate the 4 mounting screws in the 4
corners of the rear plate. Loosen these 4 screws. Lift
the entire assembly up and out of the enclosure.
Step 5:
Prior to proceeding, reference the following figures
which show the location of the mounting holes and
allowed conduit entry locations for each cabinet
type.
Step 6:
Orient the enclosure so that the "UP" arrow on the
label inside the enclosure is pointing up. Note that
the high-voltage conduit access is through the right
end of the bottom, the right side and the right end
of the top. Note that the low-voltage (Class 2)
conduit access is through the top end of the left side
and the left end of the top. Cut or punch the desired
conduit openings. Do not cut openings in the back
of the enclosure or the bottom end of the left side or
the left end of the bottom as it will no longer be
possible to re-install the electrical assembly.
WEB
VERSION
Содержание Z-MAX r24sd
Страница 2: ...WEB VERSION...
Страница 6: ...Table of Contents Page vi WEB VERSION...
Страница 14: ...Page 8 WEB VERSION...
Страница 56: ...Page 50 WEB VERSION...
Страница 62: ...Page 56 WEB VERSION...
Страница 66: ...Page 60 WEB VERSION...
Страница 72: ...Page 66 WEB VERSION...
Страница 90: ...Page 84 WEB VERSION...
Страница 92: ...WEB VERSION...