Error messages
Possible causes and remedies
42
Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.2
Possible causes and remedies
This chapter contains all error messages of the Communication Unit in numerical order of the error
number. Possible causes and remedies as well as responses to the error messages are described in
detail.
Short overview of the POWERLINK error messages
EPL: Lost connection to 8400 target [0x01bc3100]
EPL: NV Memory: No access [0x01bc5531]
EPL: NV Memory: Read error [0x01bc5532]
EPL: NV Memory: Write error [0x01bc5533]
EPL: Restart after watchdog reset [0x01bc6010]
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Communication to the Inverter Drive 8400 motec is
interrupted.
• The Inverter Drive 8400 motec is switched off.
• The Communication Unit is not connected correctly
to the Drive Unit.
• Switch on Inverter Drive 8400 motec.
• Check connection of the Communication Unit to the
Drive Unit.
• Sent Inverter Drive 8400 motec with error description
to Lenze.
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Access to parameter set in memory module via standard
device was not successful.
Download application again (including module).
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Parameter in the memory module could not be read.
Download application again (including module).
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Parameter in the memory module could not be written. Download application again (including module).
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Communication unit is defective.
Send Communication Unit with error description to
Lenze.