Commissioning
Node address (node ID) setting
26
Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2
Node address (node ID) setting
The POWERLINK node address (node ID) can either be defined via the DIP switches of the Drive Unit
or set in the »EASY Starter«/»Engineer« in code
.
• If you set the node via DIP switches, the Drive Unit cannot be configured anymore via the DIP
switches DIP1, DIP2 and the potentiometers P1, P2, P3.
• In case of the following DIP switch settings, the node ID is obtained from
• DIP1, switch 1 is "ON"
• DIP1, switch 1 is "OFF" and DIP2, switch 1 ... 8 are "OFF" (Lenze setting).
• The node IDs must differ from each other in case of several networked POWERLINK nodes.
• Save the changed parameter settings with the device command
C00002/11
(save all parameter
sets).
DIP switches of the Drive Unit
Note!
• The DIP switches can only be accessed when the drive unit is detached from the
communication unit. Loosen the four fixing screws at the drive unit.
Observe the
notes in the mounting instructions.
• Switch off the voltage supply of the controller and the external supply of the
communication unit before starting with the disassembly of the drive unit.
• The DIP switches are only read in when the device is switched on.
DIP switches of the Drive Unit 0.37 ... 3 kW
DIP1
DIP switches for configuring the Drive Unit or for setting the POWERLINK node address
DIP2