Parameter reference
Communication-relevant parameters of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11
Parameter reference
This chapter complements the parameter list and the table of attributes in the software manual and
the »Engineer« online help for the Inverter Drive 8400 motec by the parameters for POWERLINK
communication.
11.1
Communication-relevant parameters of the operating system
This chapter lists the communication-relevant parameters of the inverter operating system in nu-
merically ascending order.
C01501
C01503
Reference manual/online help for the Inverter Drive 8400 motec.
Here you will find general information on parameters.
Parameter | Name:
C01501 | Resp. to communication error with MCI
Data type: UNSIGNED_8
Index: 23074
d
= 5A22
h
Configuration of monitoring functions for the Communication Unit
Selection list
0 No response
1 Error
4 Warning Locked
Subcodes
Lenze setting
Info
C01501/1
1: No Response
Resp. to MCI fault 1
• Response to a communication fault.
C01501/2
1: No Response
Resp. to MCI fault 2
• Response to a fault in the Communication Unit.
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C01503 | MCI timeout
Data type: UNSIGNED_16
Index: 23072
d
= 5A20
h
Setting range
(min. value | unit | max. value)
0
ms
1000
Subcodes
Lenze setting
Info
C01503/1
200 ms
MCI timeout
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1