Error messages
Possible causes and remedies
44
Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EPL: Invalid module configuration [0x01bc6430]
EPL: State OPERATIONAL lost [0x01bc8131]
EPL: Invalid address selected [0x01bc8261]
EPL: Synchronisation lost from MN [0x01bc8265]
EPL: Telegram error detected (CRC) [0x01bc8266]
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Module configuration is faulty.
Check and correct module configuration.
Response
(Lenze setting printed in bold)
Setting:
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Data exchange via POWERLINK has been terminated.
• Also see the chapter "
• Check the network cable (plug) and replace it if
necessary.
• Plug the network cable into the POWERLINK terminal
X251 or X252 and continue to check the status of the
managing node.
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
An invalid IP address has been assigned by the managing
node via POWERLINK or set as node ID.
• Ensure that a valid IP address is assigned by the
managing node via POWERLINK.
• Set valid node ID.
Node address (node ID) setting (
Response
(Lenze setting printed in bold)
Setting:
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
In the controlled node, the synchronisation cycle of the
managing node has failed. The controlled node changes
automatically to the NMT_CS_PREOPERATIONAL_1
state and waits for a new run-up by the managing node.
• Check network cable and components (failure of
managing node, router).
• Restart managing node if required.
Response
(Lenze setting printed in bold)
Setting:
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
Faulty telegrams (CRC error) have been detected.
Possible causes:
• A device in the network is not EPL-compliant.
• EMC interference is too strong.
• Check if a non-EPL-compliant device is in the network
(e.g. diagnostics PC).
• Reduce EMC interference on the network or use an
additional shield connection.