9300 Servo PLC
System blocks
2.12
MCTRL_MotorControl
2-61
L
ServoPLC EN 2.0
2.12.17.6
OH - Heatsink temperature monitoring (fixed)
This monitoring function protects the controller.
No. Monitoring function
Display System variable
TRIP
Message Warning
Off
050 Heatsink temperature (fixed)
OH
MCTRL_bKuehlGreaterSetValue_b
•
•
Default setting
ü
Setting possible
MCTRL_bKuehlGreaterSetValue_b
is derived from a comparator with hysteresis. The switch-off
threshold ad the hysteresis are fixed.
•
The switch-off threshold is 85 ºC
•
The hysteresis is 5 K, i.e. the temperature when it will be switched on again is 80 ºC.
Tripping can have the following causes:
Cause
Remedy
The ambient temperature is too high.
Install a blower into the switch cabinet.
The controller is overloaded in its arithmetic mean,
i.e. overload and recovery phase exceed 100%.
•
Install a blower into the switch cabinet.
•
Shorten overload phase.
•
Use a more powerful drive.
2.12.17.7
OH3 - Motor temperature monitoring (fixed)
This function protects the motor from overheating.
No. Monitoring function
Display System variable
TRIP
Message Warning
Off
053 Motor temperature (fixed)
OH3
MCTRL_bMotorTempGreaterSetValue_b
•
ü
•
Default setting
ü
Setting possible
MCTRL_bMotorTempGreaterSetValue_b
is derived from a comparator with hysteresis. The
switch-off threshold ad the hysteresis are fixed.
•
The switch-off threshold is 150 ºC
•
The hysteresis is 15 K, i.e. the temperature when it will be switched on again is 135 ºC.
This monitoring is only effective for the thermal sensor specified by Lenze as it is included in the
standard Lenze servo motor.
•
The Sub-D connectors X7 or X8 serve as inputs.
Stop!
The temperature sensor must only be connected to X7
or
X8, the other input for the temperature
sensor must not be used.
This monitoring is active in default setting and is thus triggered when you do not connect a Lenze
servo motor!
•
The response is set under C0853:
Code
LCD
Possible settings
IMPORTANT
o
Lenze
Selection
C0583 MONIT OH3
à
Configuration monitoring
à
depending on C0086
0
TRIP
3
Off
efesotomasyon.com - Lenze