9300 Servo PLC
System blocks
2.10
DIGITAL_IO
2-36
L
ServoPLC EN 2.0
2.10
DIGITAL_IO
2.10.1
Inputs_DIGITAL
Digital inputs (module number 1)
This SB reads in the signals at the terminals X5/E1 ... X5/E5 and conditions them.
C0443
X5
Inputs_DIGITAL
1
0
C0114/1...5
E3
28
E5
E1
E4
E2
1
DCTRL-X5/28
DIGIN_bIn1_b
DIGIN_bIn2_b
DIGIN_bIn5_b
DIGIN_bIn4_b
DIGIN_bIn3_b
DIGIN_bCInh_b
Fig. 2-20
Inputs_DIGITAL
VariableName
DataType
SignalType
Address
DIS
DIS format
Note
DIGIN_bCInh_b
%IX1.0.0
-
-
Controller inhibit acts directly on
the DCTRL control
DIGIN_bIn1_b
%IX1.0.1
DIGIN_bIn2_b
Bool
binary
%IX1.0.2
DIGIN_bIn3_b
Bool
binary
%IX1.0.3
C0443
bin
DIGIN_bIn4_b
%IX1.0.4
C0443
bin
DIGIN_bIn5_b
%IX1.0.5
Electrical data of the input terminals
Terminal
Use
Data
X5/28
Controller enable (RFR)
LOW level:
0 ... +4 V
X5/E1
HIGH level:
I
t
t
+13 ... +30 V
8 A
i
t ( t 24 V)
X5/E2
Interruptible*
Input current:
8 mA per input (at 24 V)
X5/E3
Freely
* Response time of the interrupt task:
X5/E4
TP signals, actual motor speed
X7 (resolver), X8 (encoder)
Freely
assignable
* Response time of the interrupt task:
< 250
µ
s
X5/E5
TP signal
X9 (master frequency input)
X5/39
Ground (GND) of digital inputs and outputs
•
The terminal polarity of inputs E1 ... E5 can be configured under C0114.
Code
LCD
Possible settings
Info
o
Lenze
Selection
o
C0114 DIGIN pol
Terminal polarity
0
HIGH active
1
LOW active
1
1
X5/E1
2
1
X5/E2
3
0
X5/E3
4
0
X5/E4
5
0
X5/E5