System bus (CAN) with Servo PLC & Drive PLC
Configuration (AIF interface)
4-6
l
PLC-Systembus EN 1.1
4.7
Reset node
Changes in the CAN baud rate, the node addresses and the identifiers are only accepted after a reset
node.
A reset node can be initiated by
•
a fresh power-on
•
a reset node command through an NMT command
•
a reset node command via the SB
CAN_Management
•
a reset node via C0358
Code
LCD
Possible settings
Info
Lenze Choice
C0358 Reset node
0
0
no function
1
CAN reset node
Reset node
4.8
Monitoring
4.8.1
Time monitoring for XCAN1_IN ... XCAN3_IN
Via C2357 you can configure a time monitoring for the inputs of process data objects XCAN1_IN ...
XCAN3_IN:
Code
LCD
Possible settings
Info
Lenze Choice
C2357 CE monit time
0
{1 msec}
65000 Monitoring time for process data
input objects
1
3000
XCAN1_IN
2
3000
XCAN2_IN
3
3000
XCAN3_IN
If there was no telegram received in the defined monitoring time, you can configure the
corresponding reaction in code C2382/x:
Code
LCD
Possible settings
Info
Lenze Choice
C2382 XCAN Conf. CE
0
Off
1
Controller inhibit
2
Quick stop
Configuration monitoring
•
Controller inhibit or quick stop
are only possible with 9300
Servo PLC!
1
0
XCAN1_IN
2
0
XCAN2_IN
3
0
XCAN3_IN